• nybjtp

New Type CJRV-32X MPCB 25-32A Motor Protection Circuit Breaker

Short Description:

The CJRV series AC Motor protection circuit breaker is suitable for circuits with AC voltage up to 690V and current up to 80A. lt is used for overload, phase failure,short circuit protection, and infrequent starting control of three-phase squirrel cage asynchronous motors. It can beused for distribution line protection and infrequent load switching, and can also be used as an isolator.


Product Detail

Product Tags

Normal working and installation conditions

  • The altitude of the installation site generally does not exceed 2000m;
  • The lower limit of the ambient air temperature is generaly not lower than -5 ℃,the upper limit is generaly not higher than+40℃, and its average value within 24 hours does not exceed+35 ℃;
  • The relative humidity of the air shall not exceed 90% (at+25 ℃ ± 5 ℃ )
  • The pollution level of the surrounding environment is pollution level 3;
  • The installation category of the starter is installation category lll;
  • The inclination between the starter and the vertical installation surface shall not exceed ± 5 °;
  • Tripping level: CJRV-25 (X),CJRV-32 (X),CJRV-32H,CJRV-80:10A;
  • Rated working hours: uninterrupted working hours, eight hour working hours.

 

Features

  • Rated insulation voltage Ui (V): 690.
  • Rated working voltage Ue (V): AC230/240,AC400/415,AC440,AC500, AC690.
  • Rated frequency(Hz): 50/60.
  • Rated current of shell frame level Inm (A): 25(CJRV-25,25X),32 (CJRV-32,32X CJRV-32H), 80 (CJRV-80).
  • Rated current of the release In (A): (see Table 1).
  • Setting current regulation range: (see Table 1).
  • Rated ultimate short-circuit breaking capacity lcu (kA): (see Table 1).
  • Rated operating short-circuit breaking capacity lcs (kA): (see Table 1).
  • Rated impulse withstand voltage Uimp (V): 8000.
  • Selective categories (A or B) and usage categories: A, AC-3.
  • Before inserting the conductor (wire/conductive strip) into the terminal, the insulation length should be peeled off (mm): 10, 15 (CJRV-80).
  • Cross section area of conductor (wire/conductive bar) mm²: 1~6, 2.5~25 (CJRV2-80).
  • Maximum number of conductors (wires/conductive bars) allowed to be clamped in: 2, 1 (CJRV-80).
  • Terminal fastening screw (or bolt)size: M4,M8(CJRV-80).
  • Tightening torque of terminal fastening screws (N·m): 1.7, 6 (CJRV-80).
  • Operation frequency (times/hour): ≤ 30,≤ 25 (CJRV-80).

 

 

Table 1

Product number Rated current of release In (A) Setting current Adjustment range(A) Rated ultimate short-circuit breaking capacity lcu, rated operating short-circuit breaking capacity lcs kA Flying arc
distance
(mm)
AC 400/415V
AC 690V
AC 690V
Icu Ics Icu Ics
CJRV-25(X) 0.16 0.1~0.16 100 100 100 100 40
0.25 0.16~0.25 100 100 100 100 40
0.4 0.25~0.4 100 100 100 100 40
0.63 0.4~0.63 100 100 100 100 40
1 0.63~1 100 100 100 100 40
1.6 1~1.6 100 100 100 100 40
2.5 1.6~2.5 100 100 3 2.25 40
4 2.5~4 100 100 3 2.25 40
6.3 4~6.3 100 100 3 2.25 40
10 6~10 100 100 3 2.25 40
14 9~14 15 7.5 3 2.25 40
18 13~18 15 7.5 3 2.25 40
23 17~23 15 6 3 2.25 40
25 20~25 15 6 3 2.25 40
CJRV-32(X) 32 24~32 10 5 3 2.25 40
CJRV-32H 0.16 0.1~0.16 100 100 100 100 40
0.25 0.16~0.25 100 100 100 100 40
0.4 0.25~0.4 100 100 100 100 40
0.63 0.4~0.63 100 100 100 100 40
1 0.63~1 100 100 100 100 40
1.6 1~1.6 100 100 100 100 40
2.5 1.6~2.5 100 100 4 4 40
4 2.5~4 100 100 4 4 40
6.3 4~6.3 100 100 4 4 40
10 6~10 100 100 4 4 40
14 9~14 50 25 4 4 40
18 13~18 50 25 4 4 40
23 17~23 50 25 4 4 40
25 20~25 50 25 4 4 40
32 24~32 50 25 4 4 40
CJRV-80 25 20~25 50 17.5 4 2 50
32 23~32 50 17.5 4 2 50
40 30~40 50 17.5 4 2 50
50 37~50 50 17.5 4 2 50
65 48~65 50 17.5 4 2 50
80 63~80 50 17.5 4 2 50