Poles | Ie Rating | Uc | Power consumption | Max Power | ||
AC-7a | AC-7b | (VAC)(50Hz) | Hold on | Pull in | ||
2P | 16A | 6A | 230 | 2.1VA | 2.1VA | 2.0W |
20A | 7A | 230 | 2.1VA | 2.1VA | 2.0W | |
25A | 9A | 230 | 2.1VA | 2.1VA | 2.0W | |
32A | 12A | 230 | 2.1VA | 2.1VA | 2.0W | |
40A | 18A | 230 | 2.3VA | 2.3VA | 2.0W | |
63A | 25A | 230 | 2.3VA | 2.3VA | 2.0W | |
4P | 16A | 6A | 230 | 2.3VA | 2.3VA | 2.0W |
20A | 7A | 230 | 2.3VA | 2.3VA | 2.0W | |
25A | 9A | 230 | 2.3VA | 2.3VA | 2.0W | |
32A | 12A | 230 | 2.3VA | 2.3VA | 2.0W | |
40A | 18A | 230 | 6.0VA | 6.0VA | 5.5W | |
63A | 25A | 230 | 6.0VA | 6.0VA | 5.5W |
Auxiliary Contacts
The Auxiliary contacts are indicator contactor contacts status switch OFF or ON
AC-12 | AC-15 | DC-13 | Rated Current | ||||
C.V | C.A | C.V | C.A | C.V | C.A | ||
BMC7-AUC11 | 240V | 5A | 230V | 2A | DC 130V | 1A | 5A |
BMC7-AUC20 | 240V | 5A | 230V | 2A | DC 130V | 1A | 5A |
Spacing piece
Spacers are used to reduce the temperature rise of devices mounted side by side, it is recommended to separate electronic equipment
(temperature adjustment devices, programmable timer etc,) from electro mechanical equipment (impulse relays, contactors)
Technical specifications | |
Spacing piece | 3mm Spacing piece |
9mm Spacing piece |
Main parameter and technical performance
Power circuit | ||
Voltage rating(Ue) | 1P,2P | 250V AC |
3P,4P | 400V AC | |
Frequency | 50/60Hz | |
Endurance(O-C) | 1,000,000 cycles | |
Electrical | 100,000 cycles | |
Maximum number of switching operation a day | 100 | |
Insulation voltage(Ui) | 500V AC | |
Pollution degree | 2 | |
Rated impulse withstand voltage(Uimp) | 2.5kV(4kV for 12/24/48VAC) | |
Degree of protection (IEC 60529) | Device only | IP20 |
Device in modular enclosure | IP40 | |
Operating temperature | -5ºC~+60ºC | |
Storage temperature | -40ºC~+70ºC | |
Tropicalization(IEC 60068.1) | Treatment 2 (relative humidity 95% at 55ºC | |
ELSV compliance(Extra Low Safety Voltage)for 12/24/48vac versions | ||
The product control conforms to the SELV(safety extra low voltage)requirements |
Note:In the case of contactor mounting in a enclosure for which the interior temperature is in range between 50ºC and 60ºC,it is necessary to use a spacer, between each contactor