We rely upon strategic thinking, constant modernisation in all segments, technological advances and of course upon our employees that directly participate inside our success for Portable Solar Station , Circuit Breaker , Circuit Breaker And Rcd , We have a big inventory to fulfill our customer's demands and needs.
CE Certification Cbi Rcbo Exporter Residual Current Circuit Breaker with Overcurrent Protection CJRO2-40 – C&J Detail:
Construction and Feature
- Provides protection against earth fault/leakage current, short-circuit, overload, and function of isolation.
- Contact position indication
- Provides protection against indirect contact by human body
- Provides complementary protection against direct contact by human body.
- Effectively protects electric equipment against insulating failure
- Equipped with switched neutral and phase pole
- Provides protection against over-voltage
- Provides comprehensive protection to household and commercial distribution systems.
- S2 Shunt Tripper
- U2+O2 Over-voltage and under-voltage tripper
Technical Data
Standard |
IEC61009-1/EN61009-1 |
Type |
Electronic type |
Residual current characteristics |
AC |
Pole No |
1P+N |
Tripping curve |
B, C, D |
Rated short-circuit capacity |
6kA |
Rated current (A) |
6A, 10A, 16A, 20A, 25A, 32A |
Rated voltage |
230V AC |
Rated frequency |
50/60Hz |
Rated residual operating current(mA) |
0.03, 0.1, 0.3 |
Tripping duration |
instantaneous≤0.1s |
Electro-mechanical endurance |
4000 cycles |
Connection terminal |
pillar terminal with clamp |
Terminal Connection Height |
H1=16mm H2=21mm |
Over-voltage tripping |
280V±5% |
Connection capacity |
Flexible conductor 10mm² |
Rigid conductor 16mm² |
Installation |
On symmetrical DIN rail 35.5mm |
Panel mounting |
Overload Current Protection Characteristics
Test procedure |
Type |
Test Current |
Initial State |
Tripping or Non-tripping Time Limit |
Expected Result |
Remark |
a |
B,C,D |
1.13In |
cold |
t≥1h |
no tripping |
|
b |
B,C,D |
1.45In |
after test a |
t<1h |
tripping |
Current in the 5s in th increase of stability |
c |
B,C,D |
2.55In |
cold |
1s<t<60s |
tripping |
|
d |
B |
3In |
cold |
t≤0.1s |
no tripping |
Turn on the auxiliary switch to close the current |
C |
5In |
D |
10In |
e |
B |
5In |
cold |
t<0.1s |
tripping |
Turn on the auxiliary switch to close the current |
C |
10In |
D |
20In |
The terminology “cold state” refes to that no load is carried before testing at the reference setting temperature. |
Residual Current Action Breaking Time
Residual Current Action Breaking Time |
type |
In/A |
I△n/A |
Residual Current (I△) Is Corresponding To The Following Breaking Time (S) |
I△n |
2 I△n |
5 I△n |
5A,10A,20A,50A,100A,200A,500A |
I△t |
|
general
type |
any
value |
any
value |
0.3 |
0.15 |
0.04 |
0.04 |
0.04 |
Max Break-time |
A Type Of Trip Current Range
Lagangle(A) |
A Tripping Current(A) |
Lower Limit |
Upper Limit |
0° |
0.35 I△n |
0.14 I△n |
90° |
0.25 I△n |
135° |
0.11 I△n |
Product detail pictures:
Related Product Guide:
Always customer-oriented, and it's our ultimate goal to get not only by far the most reputable, trustable and honest supplier, but also the partner for our customers for CE Certification Cbi Rcbo Exporter Residual Current Circuit Breaker with Overcurrent Protection CJRO2-40 – C&J , The product will supply to all over the world, such as: UAE, Slovenia, Kuwait, We've a skilled sales team, they have mastered the good technology and manufacturing processes, have years of experience in foreign trade sales, with customers able to communicate seamlessly and accurately understand the real needs of customers, providing customers with personalized service and unique merchandise.
This is a reputable company, they have a high level of business management, good quality product and service, every cooperation is assured and delighted!
By James Brown from belarus - 2018.09.21 11:01
Speaking of this cooperation with the Chinese manufacturer, I just want to saywell dodne, we are very satisfied.
By Maud from Bandung - 2017.10.25 15:53