We believe that long term partnership is a result of high quality, value added service, rich experience and personal contact for Black Mcb , Black Plug In Mcb , Auto Recloser Elcb , Our company has already set up a professional, creative and responsible team to develop clients with the multi-win principle.
CE Certification Dc Rcbo Exporter Residual Current Circuit Breaker with Overcurrent Protection CJRO2-40 – C&J Detail:

Construction and Feature

  • Provides protection against earth fault/leakage current, short-circuit, overload, and function of isolation.
  • Contact position indication
  • Provides protection against indirect contact by human body
  • Provides complementary protection against direct contact by human body.
  • Effectively protects electric equipment against insulating failure
  • Equipped with switched neutral and phase pole
  • Provides protection against over-voltage
  • Provides comprehensive protection to household and commercial distribution systems.
  • S2 Shunt Tripper
  • U2+O2 Over-voltage and under-voltage tripper

 

Technical Data

Standard IEC61009-1/EN61009-1
Type Electronic type
Residual current characteristics AC
Pole No 1P+N
Tripping curve B, C, D
Rated short-circuit capacity 6kA
Rated current (A) 6A, 10A, 16A, 20A, 25A, 32A
Rated voltage 230V AC
Rated frequency 50/60Hz
Rated residual operating current(mA) 0.03, 0.1, 0.3
Tripping duration instantaneous≤0.1s
Electro-mechanical endurance 4000 cycles
Connection terminal pillar terminal with clamp
Terminal Connection Height H1=16mm  H2=21mm
Over-voltage tripping 280V±5%
Connection capacity Flexible conductor 10mm²
Rigid conductor 16mm²
Installation On symmetrical DIN rail 35.5mm
Panel mounting

 

Overload Current Protection Characteristics

Test procedure Type Test Current Initial State Tripping or Non-tripping Time Limit Expected Result Remark
a B,C,D 1.13In cold t≥1h no tripping
b B,C,D 1.45In after test a t<1h tripping Current in the 5s in th increase of stability
c B,C,D 2.55In cold 1s<t<60s tripping
d B 3In cold t≤0.1s no tripping Turn on the auxiliary switch to close the current
C 5In
D 10In
e B 5In cold t<0.1s tripping Turn on the auxiliary switch to close the current
C 10In
D 20In
The terminology  “cold state” refes to that no load is carried before testing at the reference setting temperature.

 

Residual Current Action Breaking Time

Residual Current Action Breaking Time
type In/A I△n/A Residual Current (I△) Is Corresponding To The Following Breaking Time (S)
I△n 2 I△n 5 I△n 5A,10A,20A,50A,100A,200A,500A I△t
general
type
any
value
any
value
0.3 0.15 0.04 0.04 0.04 Max Break-time

 

A Type Of Trip Current Range

Lagangle(A) A Tripping Current(A)
Lower Limit Upper Limit
0.35 I△n 0.14 I△n
90° 0.25 I△n
135° 0.11 I△n

Product detail pictures:


Related Product Guide:

We not only will try our great to supply outstanding services to every shopper, but also are ready to receive any suggestion offered by our buyers for CE Certification Dc Rcbo Exporter Residual Current Circuit Breaker with Overcurrent Protection CJRO2-40 – C&J , The product will supply to all over the world, such as: Croatia, South Korea, Uzbekistan, We believe with our consistently goodservice you can get the good performance and cost least goods from us for a long term . We commit to provide better services and create more value to all our customers. Hope we can create a better future together.
The company comply with the contract strict, a very reputable manufacturers, worthy a long-term cooperation.
5 Stars By Astrid from Lithuania - 2017.05.21 12:31
The accounts manager made a detailed introduction about the product, so that we have a comprehensive understanding of the product, and ultimately we decided to cooperate.
5 Stars By Vanessa from Angola - 2017.04.18 16:45
Write your message here and send it to us