With a positive and progressive attitude to customer's curiosity, our organization repeatedly improves our products high quality to meet the wants of consumers and further focuses on safety, reliability, environmental necessities, and innovation of Charging Inverter , Abb Rcd Breakers , Single Pole Rccb , We'll do our greatto fulfill your specifications and are sincerely searching ahead to developing mutual helpful small business marriage with you!
CE Certification Mcb Electrical Manufacturer - Miniature Circuit Breaker (MCB) CJM2-125 – C&J Detail:
Construction and Feature
- High short-short capacity 10KA
- Designed to protect circuit carrying big current up to 125A
- Contact position indication
- Used as main switch in household and similar installation
- The price-quality ratio is very high
Specification
Standard |
IEC/EN 60898-1 |
Pole No |
1P,1P+N, 2P, 3P,3P+N,4P |
Rated voltage |
AC 230V/400V |
Rated Current(A) |
20A,25A,32A,40A,50A,63A,80A,100A,125A |
Tripping curve |
C, D |
Rated short-circuit capacity(lcn) |
10000A |
Rated service short-circuit capacity(Ics) |
7500A |
Rated frequency |
50/60Hz |
Rated impulse withstand voltage Uimp |
6kV |
Connection terminal |
Pillar terminal with clamp |
Electro-mechanical endurance |
Ins100=10000:n125=8000 |
Terminali Connection Height |
20mm |
Connection capacity |
Flexible conductor 35mm² |
Rigid conductor 50mm² |
Installation |
On symmetrical DIN rail 35mm |
Panel mounting |
Overload Current Protection Characteristics
Test |
Tripping Type |
Test Current |
Initial State |
Tripping timeor Non-tripping Time Provisior |
a |
Time-delay |
1.05In |
Cold |
t≤1h(In≤63A)
t≤2h(ln>63A) |
No Tripping |
b |
Time-delay |
1.30In |
After test a |
t<1h(In≤63A)
t<2h(In>63A) |
Tripping |
c |
Time-delay |
2In |
Cold |
10s<t<60s(In≤63A)
20s<t<120s(In>63A) |
Tripping |
d |
Instantaneous |
8ln |
Cold |
t≤0.2s |
No Tripping |
e |
lnstantaneous |
12In |
Cold |
t<0.2s |
Tripping |
Working Principle of MCB
When an MCB is subject to continuous over-current, the bimetallic strip heats up and bends. An electromechanical latch is released when the MCB deflects the bi-metallic strip. When the user connects this electromechanical clasp to the working mechanism, it opens the microcircuit breaker contacts. Consequently, it causes the MCB to switch off and terminate the current flowing. The user should individually switch on the MCB to restore the current flow. This device guard against defects caused by excessive current, overload, and short circuits.
Product detail pictures:
Related Product Guide:
We take customer-friendly, quality-oriented, integrative, innovative as objectives. Truth and honesty is our administration ideal for CE Certification Mcb Electrical Manufacturer - Miniature Circuit Breaker (MCB) CJM2-125 – C&J , The product will supply to all over the world, such as: Turkey, Costa rica, Angola, We believe that good business relationships will lead to mutual benefits and improvement for both parties. We've got established long-term and successful cooperative relationships with many customers through their confidence in our customized services and integrity in doing business. We also enjoy a high reputation through our good performance. Better performance might be expected as our principle of integrity. Devotion and Steadiness will remain as ever.