We aim to find out high quality disfigurement in the generation and provide the most effective services to domestic and abroad clients wholeheartedly for Bg Afdd , Ac Portable Power Station , Dc Arc Fault Detection Device , We maintain timely delivery schedules, impressive designs, high-quality and transparency for our buyers. Our moto is to deliver high quality solutions within stipulated time.
CE Certification Overload Circuit Breaker Manufacturer - Intelligent Universal Breaker CJW1(ACB) – C&J Detail:
Classification
- According to the mounting: fixed and draw-out
- According to the poles: three poles, four poles
- According to the operation ways: motor and manual (maintenance and repair)
- According to the release: inteligent over current controller,under-voltage instantaneous (or delay) release,and shunt release
- The capability of the intelligent over-current controller:
- classification: H type (normal), M type (normal intelligent), L type (economic)
- has the function of overload long delay reverse time limit protection
- single phase earthed protective function
- indication function: setting current indication, action current indication, each wire voltage indication(should mention as you order).
- Alarm function
- Self- diagnostics function
- Test function
Environment Condition for Operation and Installation
- Ambient temperature: -5℃ ~ 40℃, and average temperature in 24 hours below +35℃ (except for special orders).
- Elevation of installation site: ≤2000m.
- Relative humidity: Not exceeding 50% at he maximum ambient temperature of +40℃. With lower temperature, higher humidity would be permitted, but the lowest average temperaure in a montn not exceeding +25℃ during the most moist month, and the maximum monthly average relative numiaty not exceeding 90% in that month, and giving consideration to the dews on the goods surface, which would appear due to temperature change.
- Pollution protection: 3 degree.
- Installing categories: Ⅳ for breaker’s main circuits, coils of under voltage release and primary circuit of transformers; Ⅲ for other auxiliary circuits and control circuit.
- The breakers used in ships and in humid tropical area can work normally without influence of humid air,salt fog and mildew.
- The breakers used in ships can operate reliably under normal vibration.
- The breaker should be installed according to stipulations in operation manual. For breakers in common use, the vertical gradient is not more than 50, for that used on ships, the vertical gradient is not morethan 22.50.
- The breaker should be put in the place where there is not any explosive medium and conductive dustand no gas, which would corrode metal or destroy the insulation.
- The breaker should be installed in compartment of switchboard and doorframe should be fixed additionally,protection grade is up to lP40.
Technical Data and Capability
Rated current Table 1 |
Rated frame current Inm A |
Rated current ln A |
2000 |
(400)630,800,1000,1250,1600,2000 |
3200 |
2000,2500,2900,3200 |
4000 |
3200,3600,4000 |
6300 |
4000,5000,6300 |
The rated short circuit breaking capability and short time withstand of the breakers, the arcing distance is “zero” (as the outside of the breaker is no arcing.)Table 2
Rated frame current Inm A |
|
2000 |
3200 |
4000 |
6300 |
Rated limit short circuit breaking capability
lcu(kA)O-CO |
400V |
80 |
80 |
100 |
120 |
690V |
50 |
50 |
75 |
85 |
Rated working short circuit breaking capability
n x lcu(KA)/COS∅ |
400V |
176/0.2 |
176/0.2 |
220/0.2 |
264/0.2 |
690V |
105/0.25 |
105/0.25 |
165/0.2 |
187/0.2 |
Rated short time withstand lcw
lcs(kA)O-CO-CO |
400V |
50 |
50 |
80 |
100 |
690V |
40 |
40 |
65 |
75 |
Rated short time withstand lcw
(kA)———”+0.4s,O-CO |
400V |
50 |
50 |
65/80(MCR) |
85/100(MCR) |
690V |
40 |
40 |
50/65(MCR) |
65/75(MCR) |
Notice: The input and out put wire are the same for the breaking of the capability. |
The maximum destroy power is 360W for the breakers, and in the different temperature,and rated lasting current will change.Table 3
Ambient
temperature℃ |
Rated current |
400A |
630A |
800A |
1000A |
1250A |
1600A |
2000A |
40 |
400A |
630A |
800A |
1000A |
1250A |
1600A |
2000A |
50 |
400A |
630A |
800A |
1000A |
1250A |
1550A |
1900A |
60 |
400A |
630A |
800A |
1000A |
1250A |
1550A |
1800A |
Intelligent over current controller protection feature and functions The setting and error.Table 4
Long delay |
Short delay |
Instantaneous |
Earthed error |
lr1 |
lr2 |
Error |
lr3 |
Error |
lr4 |
Error |
(0.4-1)In |
(0.4-15)In |
±10% |
ln-50kA(Inm=2000A)
ln-75kA(Inm=3200A) |
±15% |
lnm=2000~3200A
(0.2-0.8)In
(1200A,160A) |
±10% |
Notice:lf it has the three steps protection at the same time, the setting will not across. |
Long delay over current inverse time ooperation features I2TL, =(1.51lr1)2tL, and its action time(1.02-2.0) Ir1, has time error is ±15%. Table 5
1.05Ir1 |
1.3Ir1 |
1.5Ir1
Setting time S |
15 |
30 |
60 |
120 |
240 |
480 |
>2hno action |
<1h action |
2.0Ir Setting time S |
8.4 |
16.9 |
33.7 |
67.5 |
135 |
270 |
Product detail pictures:
Related Product Guide:
Our enterprise since its inception, constantly regards product good quality as organization life, constantly improve production technology, strengthen merchandise high quality and continuously strengthen enterprise total good quality administration, in strict accordance with all the national standard ISO 9001:2000 for CE Certification Overload Circuit Breaker Manufacturer - Intelligent Universal Breaker CJW1(ACB) – C&J , The product will supply to all over the world, such as: Algeria, Tanzania, Curacao, Our company's main items are widely used all over the world; 80% of our products and solutions exported to the United States, Japan, Europe and other markets. All stuff sincerely welcome guests come to visit our factory.