Model:EFP | 33224 | 43224 | 63248 | 83248 | 103248 | 123248 |
PV Input | ||||||
Max PV Input Power | 5000W | 7000W | 4500W*2 | 6000W*2 | 6000W*2 | |
MPPT Tracking Voltage Range | 40Vdc-450Vdc | 80Vdc-450Vdc | ||||
Rated Voltage | 360Vdc | |||||
Max PV Input Voltage voc(at the lowest temperature) | 500Vdc | |||||
Max PV Input Current | 18A | 22A | 18A*2 | 22A*2 | 27A*2 | |
MPPT Tracking Channels (Input Routed) | 1 Routed | 2 Routed | ||||
Battery &Charging | ||||||
Battery Type | Lead-acid Battery Lithium Battery | |||||
Custom Battery (Charging and discharging parameter of different types of batteries can be set through the operation board) | ||||||
Rated Battery Voltage | 24Vdc | 48Vdc | ||||
Battery voltage Range | 21~30Vdc(default) | 42~60Vdc(default) | ||||
Max PV Charging Curent | 120A | 150A | 120A | 150A | 180A | 200A |
Max AC Charging Current | 80A | 100A | 80A | 100A | 120A | 140A |
Max Charging Current | 120A | 150A | 120A | 150A | 180A | 200A |
Grid-Connected Operation (Grid-Connected Output (AC)) | ||||||
Rated Output Power | 3300W | 4300W | 6300W | 8300W | 10.3KW | 12.3KW |
Rated Output Voltage | 220Vac/230Vac/240Vac | |||||
Grid Voltage Range | 187Vac~264Vac | |||||
Rated Output Frequency | 50Hz/60Hz | |||||
Frequency Range | 47Hz-52Hz(50Hz),57Hz-62Hz(60Hz) | |||||
Rated Output Current | 14.5A/13.9A/13.3A | 19.5A/18.7A/17.9A | 28.6A/27.4A/26.2A | 37.7A/36.1A/34.6A | 46.7A/44.9A/42.9A | 55.9A/53.5A/51.3A |
Power Factor | >0.98(Rated Power) | |||||
Off-Grid Operation(AC Input) | ||||||
Rated Input voltage | 220V/230V/240V | |||||
Mains input voltage range | 165Vac-280Vac/120Vac-280Vac(Can be set) | |||||
Rated Input Frequency | 50Hz/60Hz | |||||
Input Frequency Range | 45Hz-55Hz(50Hz),55Hz-65Hz(60Hz) | |||||
AC Output | ||||||
Rated Output Power | 3300W | 4300W | 6300W | 8300W | 10.3KW | 12.3KW |
Rated Output Voltage | 220V/230V/240V | |||||
Output Voltage Accuracy | ±2% | |||||
Rated Input Frequency | 50Hz /60Hz | |||||
Output Frequency Accuracy | ±1% | |||||
Output Wave | Pure Sine Wave | |||||
Mixed Operation (Complementary Mode(AC Input)) | ||||||
Rated Input voltage | 220V/230V/240V | |||||
Mains input voltage range | 187Vac~264Vac | |||||
Rated Input Frequency | 50Hz /60Hz | |||||
Input Frequency Range | 47Hz~52Hz(50Hz),57Hz-62Hz(60Hz) | |||||
AC Output | ||||||
Rated Output Power | 3300W | 4300W | 6300W | 8300W | 10.3KW | 12.3KW |
Rated Voltage Rated | 220Vac/230Vac/240Vac | |||||
Output Current | 14.5A/13.9A/13.3A | 19.5A/18.7A/17.9A | 28.6A/27.4A/26.2A | 37.7A/36.1A/34.6A | 46.7A/44.9A/42.9A | 55.9A/53.5A/51.3A |
General parameters | ||||||
Maximum Conversion Efficiency(Battery discharge) | 94%(peak value) | |||||
MPPT Tracking Efficiency | ≥99.9 | |||||
Transfer Time | 10ms(Typical value) | |||||
Display | LCD+LED | |||||
Cooling Method | Cooling fan in intelligent control | |||||
Communication | RS485/Mobile APP(WIFI Monitoring or GPRS monitoring)(Optional) | |||||
Protection Degree | IP20 | |||||
Installation | Wall-Mounted | |||||
Protection | ||||||
Battery low voltage alarm | 22Vdc (default value) | 44Vdc(default value) | ||||
Battery low voltage protection | 21Vdc (default value) | 42Vdc(default value) | ||||
Anti-islanding protection | ≤2S | |||||
Overload power protection | Automatic Protection (battery mode),Circuit Breaker or Insurance(AC mode) | |||||
Output short circuit protection | Automatic Protection (battery mode),Circuit Breaker or Insurance(AC mode) | |||||
Temperature protection | >90°C(turn off inverter and charging) | |||||
Environment | ||||||
Operating temperature | 10°C~50°C | |||||
Storage temperature | 15°C-60°C | |||||
Noise | ≤55dB | |||||
Elevation | 2000m(More than derating) | |||||
Humidity | 0%-95%,No condensation | |||||
Dimensions and Weight | ||||||
Product Size(L*W*H mm) | 325*275*102 | 365*297*102 | 390*320*112 | 515*365*117 | 535*462*117 | 630*540*130 |
Package Size(L*W*H mm) | 400*330*167 | 440*352*167 | 465*375*187 | 600*430*192 | 615*527*192 | 715*605*205 |
N.W. (kg) | 6 | 6.5 | 10.5 | 13 | 17 | 23.5 |
G.W. (kg) | 6.5 | 7 | 12 | 15 | 19 | 25.5 |
Note:1.Specfications are subject to change wthout prior notice; 2.Special voltage and power requirements can be customized according to the actual situation of users. |