Mode | Electro-magnetic type, electronic type |
Residual current characteristics | A, AC |
Pole No. | 2P, 4P |
Rated making and breaking capacity | 500A(In=25A,32A,40A) or 630A(In=63A) |
Rated current(A) | 16, 25, 40, 63 |
Rated voltage | AC 230/400V |
Rated frequency | 50/60Hz |
Rated residual operating current I△n(A) | 0.03, 0.1, 0.3, 0.5 |
Rated residual non operating current I△no | 0.5I△n |
Rated conditional short-circuit current Inc | 10kA |
Rated conditional residual short-circuit current I△c | 10kA |
Residual tripping current range | 0.5I△n~I△n |
Terminal Connection Height | 21mm |
Electro-mechanical endurance | 4000 cycles |
Connection capacity | Rigid conductor 25mm² |
Connection terminal | Screw terminal |
Pillar terminal with clamp | |
Fastening torque | 2.0N.m |
Installation | On symmetrical DIN rail 35.5mm |
Panel mounting | |
Protection class | IP20 |
Type | In/A | I△n/A | Residual Current (I△) Is Corresponding To The Following Breaking Time (S) | ||||
I△n | 2 I△n | 5 I△n | 5A,10A,20A,50A,100A,200A,500A | ||||
general type | any value | any value | 0.3 | 0.15 | 0.04 | 0.04 | Max Break-time |
S Type | ≥25 | >0.03 | 0.5 | 0.2 | 0.15 | 0.15 | Max Break-time |
0.13 | 0.06 | 0.05 | 0.04 | Min non-driving time | |||
The general type RCBO whose current IΔn is 0.03mA or less can use 0.25A instead of 5IΔn. |