Technical Data
Model |
CJ-T2-100/4P |
CJ-T2-100/3+NPE |
IEC category |
II,T2 |
II,T2 |
SPD category |
Voltage-limiting type |
Combination type |
Specifications |
1P/2P/3P/4P |
1+NPE/3+NPE |
Rated voltage Uc |
220VAC/220VAC/380VAC/380VAC |
380VAC/220VAC/385VAC |
Maximum continuous operating voltage Uc |
275VAC/385VAC |
385VAC/275VAC/385VAC |
Nominal discharge current In (8/20)μS L-N |
60KA |
Maximum discharge current Imax (8/20)μS L-N |
100KA |
Voltage protection level Up (8/20)μS L-N |
2.5KV |
Short circuit tolerance 1 |
300A |
Response time tA N-PE |
≤25ns |
Backup protection SCB selection |
CJSCB-100 |
Failure indication |
Green: normal; Red: failure |
Installation conductor cross-sectional area |
4-35mm2 |
Installation method |
35mm standard rail (EN50022/DIN46277-3) |
Working environment |
-40~70°C |
Casing material |
Plastic, UL94V-0 compliant |
Protection level |
IP20 |
Testing standard |
IEC61643-1/GB18802.1 |
Accessories can be added |
Remote signal alarm, remote signal interface wiring capability |
Accessory attributes |
NO/NC contact terminal (optional), maximum 1.5mm² single strand/flexible wire |