The main technical parameters
Table 1
Model | Fastener rated current In (A) |
Tuning current adjustment range (A) |
Rated limit short-circuit breaking capability Icu rated operation short-circuit breaking capability Ics kA |
Arcing distance (mm) |
|||
400/415V | 690V | ||||||
Icu | Ics | Icu | Ics | ||||
GV2-ME32(X/P) | 0.16 | 0.1~0.16 | 100 | 100 | 100 | 100 | 40 |
GV2-ME32(X/P) | 0.25 | 0.16~0.25 | 100 | 100 | 100 | 100 | 40 |
GV2-ME32(X/P) | 0.4 | 0.25~0.4 | 100 | 100 | 100 | 100 | 40 |
GV2-ME32(X/P) | 0.63 | 0.4~0.63 | 100 | 100 | 100 | 100 | 40 |
GV2-ME32(X/P) | 1 | 0.63~1 | 100 | 100 | 100 | 100 | 40 |
GV2-ME32(X/P) | 1.6 | 1~1.6 | 100 | 100 | 100 | 100 | 40 |
GV2-ME32(X/P) | 2.5 | 1.6~2.5 | 100 | 100 | 3 | 2.25 | 40 |
GV2-ME32(X/P) | 4 | 2.5~4 | 100 | 100 | 3 | 2.25 | 40 |
GV2-ME32(X/P) | 6.3 | 4~6.3 | 100 | 100 | 3 | 2.25 | 40 |
GV2-ME32(X/P) | 10 | 6~10 | 100 | 100 | 3 | 2.25 | 40 |
GV2-ME32(X/P) | 14 | 9~14 | 15 | 7.5 | 3 | 2.25 | 40 |
GV2-ME32(X/P) | 18 | 13~18 | 15 | 7.5 | 3 | 2.25 | 40 |
GV2-ME32(X/P) | 23 | 17~23 | 15 | 6 | 3 | 2.25 | 40 |
GV2-ME32(X/P) | 25 | 20~25 | 15 | 6 | 3 | 2.25 | 40 |
GV2-ME32(X/P) | 32 | 24~32 | 10 | 6 | 3 | 2.25 | 40 |
GV3-ME80 | 25 | 16~25 | 15 | 7.5 | 4 | 2 | 50 |
GV3-ME80 | 40 | 25~40 | 15 | 7.5 | 4 | 2 | 50 |
GV3-ME80 | 63 | 40~63 | 15 | 7.5 | 4 | 2 | 50 |
GV3-ME80 | 80 | 56~80 | 15 | 7.5 | 4 | 2 | 50 |
Table 2
Model | Fastener rated current In (A) | Tuning current adjustment range (A) |
Standard rated power of three-phase motor (kw) | |||||
AC-3,50Hz/60Hz | ||||||||
230/240V | 400V | 415V | 440V | 500V | 690V | |||
GV2-ME32(X/P) | 0.16 | 0.1~0.16 | - | - | - | - | - | - |
GV2-ME32(X/P) | 0.25 | 0.16~0.25 | - | - | - | - | - | - |
GV2-ME32(X/P) | 0.4 | 0.25~0.4 | - | - | - | - | - | - |
GV2-ME32(X/P) | 0.63 | 0.4~0.63 | - | - | - | - | - | 0.37 |
GV2-ME32(X/P) | 1 | 0.63~1 | - | - | - | 0.37 | 0.37 | 0.55 |
GV2-ME32(X/P) | 1.6 | 1~1.6 | - | 0.37 | - | 0.55 | 0.75 | 1.1 |
GV2-ME32(X/P) | 2.5 | 1.6~2.5 | 0.37 | 0.75 | 0.75 | 1.1 | 1.1 | 1.5 |
GV2-ME32(X/P) | 4 | 2.5~4 | 0.75 | 1.5 | 1.5 | 1.5 | 2.2 | 3 |
GV2-ME32(X/P) | 6.3 | 4~6.3 | 1.1 | 2.2 | 2.2 | 3 | 3.7 | 4 |
GV2-ME32(X/P) | 10 | 6~10 | 2.2 | 4 | 4 | 4 | 5.5 | 7.5 |
GV2-ME32(X/P) | 14 | 9~14 | 3 | 5.5 | 5.5 | 7.5 | 7.5 | 9 |
GV2-ME32(X/P) | 18 | 13~18 | 4 | 7.5 | 9 | 9 | 9 | 11 |
GV2-ME32(X/P) | 23 | 17~23 | 5.5 | 11 | 11 | 11 | 11 | 15 |
GV2-ME32(X/P) | 25 | 20~25 | 5.5 | 11 | 11 | 11 | 15 | 18.5 |
GV2-ME32(X/P) | 32 | 24~32 | 7.5 | 15 | 15 | 15 | 18.5 | 25 |
GV3-ME80 | 25 | 16~25 | - | 11 | 11 | - | - | 18.5 |
GV3-ME80 | 40 | 25~40 | - | 18.5 | 18.5 | - | - | 37 |
GV3-ME80 | 63 | 40~63 | - | 30 | 30 | - | - | 55 |
GV3-ME80 | 80 | 56~80 | - | 37 | 37 | - | - | 63 |
Table 3
Model | Rack rated current Inm A |
Hourly operation cycles |
Operation cycle number | |
Electrical life | Mechanical Life | |||
GV2-ME32(X/P) | 32 | 120 | 10000 | 100000 |
GV3-ME80 | 80 | 120 | 1500 | 8500 |