Standard | IEC/EN 60898-1 | ||||
Pole No | 1P,1P+N, 2P, 3P,3P+N,4P | ||||
Rated voltage | AC 230V/400V | ||||
Rated Current(A) | 1A,2A,3A,4A,6A,10A,16A,20A,25A,32A,40A,50A,63A | ||||
Tripping curve | B, C, D | ||||
Rated short-circuit capacity(lcn) | 6000A | ||||
Rated frequency | 50/60Hz | ||||
Rated impulse withstand voltage Uimp | 4kV | ||||
Connection terminal | Pillar terminal with clamp | ||||
Mechanical life | 20,000 Cycles | ||||
Electrical life | 4000 Cycles | ||||
Protection degree | IP20 | ||||
Connection capacity | Flexible conductor 35mm² | ||||
Rigid conductor 50mm² | |||||
Installation | On symmetrical DIN rail 35mm | ||||
Panel mounting |
Test | Tripping Type | Test Current | Initial State | Tripping timeor Non-tripping Time Provisior | |
a | Time-delay | 1.13In | Cold | t≤1h(In≤63A) t≤2h(ln>63A) |
No Tripping |
b | Time-delay | 1.45In | After test a | t<1h(In≤63A) t<2h(In>63A) |
Tripping |
c | Time-delay | 2.55In | Cold | 1s<t<60s(In≤63A) 1s<t<120s(In>63A) |
Tripping |
d | B curve | 3In | Cold | t≤0.1s | No Tripping |
C curve | 5In | Cold | t≤0.1s | No Tripping | |
D curve | 10In | Cold | t≤0.1s | No Tripping | |
e | B curve | 5In | Cold | t≤0.1s | Tripping |
C curve | 10In | Cold | t≤0.1s | Tripping | |
D curve | 20In | Cold | t≤0.1s | Tripping |