Our primary objective is usually to offer our shoppers a serious and responsible small business relationship, offering personalized attention to all of them for Portable Outdoor Power Station , Residual Current Breaker With Overcurrent Protection , C Curve Mcb , Our tenet is Reasonable prices, economical production time and very good service We hope to cooperate with much more shoppers for mutual enhancement and benefits.
China OEM Rcbo Residual Circuit Breaker Manufacturer - Intelligent Universal Breaker CJW1(ACB) – C&J Detail:
Classification
- According to the mounting: fixed and draw-out
- According to the poles: three poles, four poles
- According to the operation ways: motor and manual (maintenance and repair)
- According to the release: inteligent over current controller,under-voltage instantaneous (or delay) release,and shunt release
- The capability of the intelligent over-current controller:
- classification: H type (normal), M type (normal intelligent), L type (economic)
- has the function of overload long delay reverse time limit protection
- single phase earthed protective function
- indication function: setting current indication, action current indication, each wire voltage indication(should mention as you order).
- Alarm function
- Self- diagnostics function
- Test function
Environment Condition for Operation and Installation
- Ambient temperature: -5℃ ~ 40℃, and average temperature in 24 hours below +35℃ (except for special orders).
- Elevation of installation site: ≤2000m.
- Relative humidity: Not exceeding 50% at he maximum ambient temperature of +40℃. With lower temperature, higher humidity would be permitted, but the lowest average temperaure in a montn not exceeding +25℃ during the most moist month, and the maximum monthly average relative numiaty not exceeding 90% in that month, and giving consideration to the dews on the goods surface, which would appear due to temperature change.
- Pollution protection: 3 degree.
- Installing categories: Ⅳ for breaker’s main circuits, coils of under voltage release and primary circuit of transformers; Ⅲ for other auxiliary circuits and control circuit.
- The breakers used in ships and in humid tropical area can work normally without influence of humid air,salt fog and mildew.
- The breakers used in ships can operate reliably under normal vibration.
- The breaker should be installed according to stipulations in operation manual. For breakers in common use, the vertical gradient is not more than 50, for that used on ships, the vertical gradient is not morethan 22.50.
- The breaker should be put in the place where there is not any explosive medium and conductive dustand no gas, which would corrode metal or destroy the insulation.
- The breaker should be installed in compartment of switchboard and doorframe should be fixed additionally,protection grade is up to lP40.
Technical Data and Capability
Rated current Table 1 |
Rated frame current Inm A |
Rated current ln A |
2000 |
(400)630,800,1000,1250,1600,2000 |
3200 |
2000,2500,2900,3200 |
4000 |
3200,3600,4000 |
6300 |
4000,5000,6300 |
The rated short circuit breaking capability and short time withstand of the breakers, the arcing distance is “zero” (as the outside of the breaker is no arcing.)Table 2
Rated frame current Inm A |
|
2000 |
3200 |
4000 |
6300 |
Rated limit short circuit breaking capability
lcu(kA)O-CO |
400V |
80 |
80 |
100 |
120 |
690V |
50 |
50 |
75 |
85 |
Rated working short circuit breaking capability
n x lcu(KA)/COS∅ |
400V |
176/0.2 |
176/0.2 |
220/0.2 |
264/0.2 |
690V |
105/0.25 |
105/0.25 |
165/0.2 |
187/0.2 |
Rated short time withstand lcw
lcs(kA)O-CO-CO |
400V |
50 |
50 |
80 |
100 |
690V |
40 |
40 |
65 |
75 |
Rated short time withstand lcw
(kA)———”+0.4s,O-CO |
400V |
50 |
50 |
65/80(MCR) |
85/100(MCR) |
690V |
40 |
40 |
50/65(MCR) |
65/75(MCR) |
Notice: The input and out put wire are the same for the breaking of the capability. |
The maximum destroy power is 360W for the breakers, and in the different temperature,and rated lasting current will change.Table 3
Ambient
temperature℃ |
Rated current |
400A |
630A |
800A |
1000A |
1250A |
1600A |
2000A |
40 |
400A |
630A |
800A |
1000A |
1250A |
1600A |
2000A |
50 |
400A |
630A |
800A |
1000A |
1250A |
1550A |
1900A |
60 |
400A |
630A |
800A |
1000A |
1250A |
1550A |
1800A |
Intelligent over current controller protection feature and functions The setting and error.Table 4
Long delay |
Short delay |
Instantaneous |
Earthed error |
lr1 |
lr2 |
Error |
lr3 |
Error |
lr4 |
Error |
(0.4-1)In |
(0.4-15)In |
±10% |
ln-50kA(Inm=2000A)
ln-75kA(Inm=3200A) |
±15% |
lnm=2000~3200A
(0.2-0.8)In
(1200A,160A) |
±10% |
Notice:lf it has the three steps protection at the same time, the setting will not across. |
Long delay over current inverse time ooperation features I2TL, =(1.51lr1)2tL, and its action time(1.02-2.0) Ir1, has time error is ±15%. Table 5
1.05Ir1 |
1.3Ir1 |
1.5Ir1
Setting time S |
15 |
30 |
60 |
120 |
240 |
480 |
>2hno action |
<1h action |
2.0Ir Setting time S |
8.4 |
16.9 |
33.7 |
67.5 |
135 |
270 |
Product detail pictures:
Related Product Guide:
Good quality comes 1st; assistance is foremost; business enterprise is cooperation is our business enterprise philosophy which is regularly observed and pursued by our company for China OEM Rcbo Residual Circuit Breaker Manufacturer - Intelligent Universal Breaker CJW1(ACB) – C&J , The product will supply to all over the world, such as: Russia, UAE, Washington, we've got all day online sales to make sure the pre-sale and after-sale service in time. With all these supports, we can serve every customer with quality product and timely shipping with highly responsibility. Being a young growing company, we might not the good, but we are trying our good to be your good partner.