We emphasize progress and introduce new solutions into the market each year for China Supplier CJW1-450-1000-3p/4p Intelligent Universal Air Circuit Breaker Acb with IEC60947-2, Together with the everlasting target of “continuous top quality improvement, customer satisfaction”, we have been sure that our products high quality is stable and trustworthy and our solutions are best-selling at your home and overseas.
We emphasize progress and introduce new solutions into the market each year for China Acb and Air Circuit Breaker, If you are interested in any of our solutions or would like to discuss a custom order, you should feel free to contact us. We have been looking forward to forming successful business relationships with new clients around the world in the near future.
Rated current Table 1 | ||||||||
Rated frame current Inm A | Rated current ln A | |||||||
2000 | (400)630,800,1000,1250,1600,2000 | |||||||
3200 | 2000,2500,2900,3200 | |||||||
4000 | 3200,3600,4000 | |||||||
6300 | 4000,5000,6300 |
The rated short circuit breaking capability and short time withstand of the breakers, the arcing distance is “zero” (as the outside of the breaker is no arcing.)Table 2
Rated frame current Inm A | 2000 | 3200 | 4000 | 6300 | ||||
Rated limit short circuit breaking capability lcu(kA)O-CO |
400V | 80 | 80 | 100 | 120 | |||
690V | 50 | 50 | 75 | 85 | ||||
Rated working short circuit breaking capability n x lcu(KA)/COS∅ |
400V | 176/0.2 | 176/0.2 | 220/0.2 | 264/0.2 | |||
690V | 105/0.25 | 105/0.25 | 165/0.2 | 187/0.2 | ||||
Rated short time withstand lcw lcs(kA)O-CO-CO |
400V | 50 | 50 | 80 | 100 | |||
690V | 40 | 40 | 65 | 75 | ||||
Rated short time withstand lcw (kA)———”+0.4s,O-CO |
400V | 50 | 50 | 65/80(MCR) | 85/100(MCR) | |||
690V | 40 | 40 | 50/65(MCR) | 65/75(MCR) | ||||
Notice: The input and out put wire are the same for the breaking of the capability. |
The maximum destroy power is 360W for the breakers, and in the different temperature,and rated lasting current will change.Table 3
Ambient temperature℃ |
Rated current | |||||||
400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A | ||
40 | 400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A | |
50 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1900A | |
60 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1800A |
Intelligent over current controller protection feature and functions The setting and error.Table 4
Long delay | Short delay | Instantaneous | Earthed error | |||||
lr1 | lr2 | Error | lr3 | Error | lr4 | Error | ||
(0.4-1)In | (0.4-15)In | ±10% | ln-50kA(Inm=2000A) ln-75kA(Inm=3200A) |
±15% | lnm=2000~3200A (0.2-0.8)In (1200A,160A) |
±10% | ||
Notice:lf it has the three steps protection at the same time, the setting will not across. |
Long delay over current inverse time ooperation features I2TL, =(1.51lr1)2tL, and its action time(1.02-2.0) Ir1, has time error is ±15%. Table 5
1.05Ir1 | 1.3Ir1 | 1.5Ir1 Setting time S |
15 | 30 | 60 | 120 | 240 | 480 |
>2hno action | <1h action | 2.0Ir Setting time S | 8.4 | 16.9 | 33.7 | 67.5 | 135 | 270 |
We emphasize progress and introduce new solutions into the market each year for China Supplier CJW1-450-1000-3p/4p Intelligent Universal Air Circuit Breaker Acb with IEC60947-2, Together with the everlasting target of “continuous top quality improvement, customer satisfaction”, we have been sure that our products high quality is stable and trustworthy and our solutions are best-selling at your home and overseas.