Technical Data
IEC Electrical |
|
|
150 |
275 |
320 |
Nominal AC Voltage (50/60Hz) |
|
Uc/Un |
120V |
230V |
230V |
Maximum Continuous Operating Voltage (AC) |
(L-N) |
Uc |
150V |
270V |
320V |
(N-PE) |
Uc |
255V |
Nominal Discharge Current (8/20μs) |
(L-N)/(N-PE) |
In |
20 kA/50kA |
Maximum Discharge Current (8/20μs) |
(L-N)/(N-PE) |
Imax |
50 kA/100 kA |
Impulse Discharge Current (10/350μs) |
(L-N)/(N-PE) |
Iimp |
12.5kA/50kA |
Specific Energy |
(L-N)/(N-PE) |
W/R |
39 kJ/Ω / 625 kJ/Ω |
Charge |
(L-N)/(N-PE) |
Q |
6.25 As/12.5As |
Voltage Protection Level |
(L-N)/(N-PE) |
Up |
1.0kV/1.5 kV |
1.5 kV/1.5 kV |
1. 6kV/1.5 kV |
|
(N-PE) |
Ifi |
100 ARMS |
Response Time |
(L-N)/(N-PE) |
tA |
<25ns/<100 ns |
Back-Up Fuse(max) |
|
|
315A/250A gG |
Short-Circuit Current Rating (AC) |
(L-N) |
ISCCR |
25kA/50kA |
TOV Withstand 5s |
(L-N) |
UT |
180V |
335V |
335V |
TOV 120min |
(L-N) |
UT |
230V |
440V |
440V |
|
|
mode |
Safe Fail |
Safe Fail |
Safe Fail |
TOV Withstand 200ms |
(N-PE) |
UT |
1200V |
UL Electrical |
|
|
|
|
|
Maximum Continuous Operating Voltage(AC) |
|
MCOV |
150V/255V |
275V/255V |
320V/255V |
Voltage Protection Rating |
|
VPR |
600V/1200V |
900V/1200V |
1200V/1200V |
Nominal Discharge Current (8/20μs) |
|
In |
20kA/20kA |
20kA/20kA |
20kA/20kA |
Short-Circuit Current Rating (AC) |
|
SCCR |
200kA |
150kA |
150kA |
Normal Working Conditions
- -Altitude not exceed 2000m
- -Ambient air temperature:
- Normal range: -5ºC~+40ºC
- Extend range: -40ºC~+80ºC
- -Relative Humidity: 30% – 90% under indoor temperature condition
- - At the place without obviously shaking and shock vibration
- - Non-explosion danger medium, non-corrosion gas and dust ( including conductive dust)