• nybjtp

CJ-C40m 2p 1.5ka 40ka DC 1000V Surge Protective Device SPD with Lighting Protection

Short Description:

 Construction and Feature

  • Location of Use:  Sub-Distribution Boards
  • Mode of Protection:  L-N, N-PE
  • Surge Ratings:  In = 20kA(8/20μs)
  • IEC/EN/UL Category:  Class I+II / Type 1+2
  • Protective Elements:  High Energy MOV and GDT
  • Housing:  Pluggable Design
  • Compliance:  IEC 61643-11:2011 / EN  61643-11:2012

 

The Surge Protective Device (SPD) is a component of the electrical installation protection system. This device connects in parallel to the power supply circuit of the loads that it has to protect. The surge protective device redirects electrical currents like nominal discharge current from a short circuit. It does that using either a solid-state contact or an air-gap switch. In addition, the surge protective device serves as a load-safe shutoff device for overcurrent conditions and a recloser that controls the voltage level above the rated voltage or low voltage in the event of a fault condition. We can also use the surge protective device at all levels of the power supply network. This approach is often the foremost commonly used and most effective sort of overvoltage protection.


Product Detail

Product Tags

Technical Data

IEC Electrical 75 150 275 320 385 440
Nominal AC Voltage (50/60Hz) 60V 120V 230V 230V 230V 400V
Maximum Continuous Operating Voltage (AC) (L-N) Uc 75V 150V 275V 320V 385V 440V
(N-PE) Uc 255V
Nominal Discharge Current (8/20μs) (L-N)/(N-PE) In 20kA/20kA
Maximum Discharge Current (8/20μs) (L-N)/(N-PE) Imax 40kA/40kA
Impulse Discharge Current (10/350μs) (L-N)/(N-PE) Iimp 7kA/25kA
Voltage Protection Level (L-N)/(N-PE) Up 0.4kV/1.5kV
Follow Current Interrupt Rating (N-PE) Ifi 100ARMS
Response Time (L-N)/(N-PE) tA <25ns/<100ns
Back-Up Fuse (max) 63A gL /gG
Short-Circuit Current Rating (AC) (L-N) ISCCR 20kA
TOV Withstand 5s (L-N) UT 90V 180V 335V 335V 335V 580V
TOV 120min (L-N) UT 115V 230V 440V 440V 440V 765V
mode Withstand Withstand Safe Fail Safe Fail Safe Fail Safe Fail
TOV Withstand 200ms (N-PE) UT 1200V
Operating Temperature Range Ta -40ºF to +158ºF[-40ºC to +70ºC]
Permissible Operating Humidity RH 5%…95%
Atmospheric pressure and altitude 80k Pa..106k Pa/-500m..2000m
Terminal Screw Torque (L-N) Mmax
(PE) Mmax 39.9 lbf-in[4.5 Nm]
Conductor Cross Section (L-N) 5 AWG(Solid, Stranded) / 7 AWG(Flexible)
16 mm2(Solid, Stranded) / 10 mm2 (Flexible)
(PE) 2 AWG(Solid, Stranded) / 4 AWG(Flexible)
35 mm²(Solid, Stranded) / 25 mm2 (Flexible)
Mounting 35 mm DIN Rail,EN 60715
Degree of Protection IP 20 (built-in)
Housing Material Thermoplastic: Extinguishing Degree UL 94 V-0
Thermal Protection Yes
Operating State / Fault Indication Green ok / Red defect
Remote Contacts (RC) Optional
RC Switching Capacity AC:250V/0.5A;DC:250V/0.1A;125V/0.2A;75V/0.5A
RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm2(Solid)
RC Terminal Screw Torque 2.2 lbf·in [0.25 Nm]

 