lt’s suitable for D grade surge protection,CJ-T2-20 series surge protective device according to GB188021.1-2002,installed on the joint of LPZ1 or LPZ2 and LPZ3.usually installed in household distribution boards,computer equipment, information equipment,electronicequipment and in the socket box in front of control equipment or near the control equipment.
·Could be replaced for the module not need power cut.
·Maximum currrent of endure the surge stroke 20kA(8/20μs).
·Time of response<25ns.
·The color of visible window shows operating status,green means normal,red means abnormal.
Model | CJ-T2-20 | |||
Rated Operating Voltage Un(V~) | 220V | 380V | 220V | 380V |
Maximum Continuous Operating Voltage Uc(V~) | 275V | 385V | 320V | 385V |
Voltage Protection Level Up(V~)kV | ≤0.7 | ≤1.0 | ≤1.2 | ≤1.5 |
Nominal Discharge Current In(8/20μs)kA | 5 | 10 | ||
Maximum Discharge Current lmax(8/20μs)kA | 10 | 20 | ||
Response Time ns | <25 | |||
Test Standard | GB18802/IEC61643-1 | |||
The Cross Section of L/N Line(mm²) | 6 | |||
The Cross Section of PE Line(mm²) | 16 | |||
Fuse or Switch(A) | 10A,16A | 16A,25A | ||
Operating Environment ºC | -40ºC~+85ºC | |||
Relative Humidity(25ºC) | ≤95% | |||
Installation | Standard Rail 35mm | |||
Material of Outer Covering | Fiber glass reinforced plastic |