• nybjtp

CJAS80 3P 80A Din-Rail installation electrical Switch Disconnector for solar system

Short Description:

CJSD80 Switch-disconnectors are widely used in Power Distribution systems and Automation systems for Buildings, Power, Petrochemical and other industries, can effectively solve the problems of emergency disconnection, safety disconnection, machine control and motor control.

With integrated isolation, breaking and switching function, the high performance design means these products can be easily changed form Load Isolation Switches to Cam Switches and provide highly innovative solutions for many application.


Product Detail

Product Tags

Technical details

Type 3P SD16R SD20R SD25R SD32R SD40R SD63R SD80R SD80HR SD100R SD125R
4P
Agreed heating current(≤40°C) 16A 20A 25A 32A 40A 63A 80A 100A 100A 125A
IEC rated operational
current Ie AC-21A/B(≤690V)
16A/16A 20A/20A 25A/25A 32A/32A 40A/40A 63A/63A 80A/80A 100A/100A 100A/100A 125A/125A
IEC rated operational current
Ie AC-22A/B
415V 16A/16A 20A/20A 25A/25A 32A/32A 40A/40A 63A/63A 80A/80A 100A/100A 100A/100A 125A/125A
500V
690V 32A/40A 40A/63A 63A/80A 63A/80A 80A/100A 100A/125A
IEC rated operational current
Ie AC-23A/B
415V 16A/16A 20A/20A 25A/25A 32A/32A 40A/40A 63A/63A 80A/80A 100A/100A 100A/100A 125A/125A
500V 25A/25A 63A/63A 80A/100A 100A/100A
690V 40A/40A 63A/63A 63A/63A
IEC rated operational current
Ie DC-21B
110VDC 16A(1) 20A(1) 25A(1) 32A(1) 40A(1) 63A(1) 80A(1) 100A(1) 100A(1) 125A(1)
250VDC 16A(2) 20A(2) 25A(2) 32A(2) 40A(2) 63A(2) 80A(2) 100A(2) 100A(2) 125A(2)
400VDC 16A(3) 20A(3) 25A(3) 25A(3) 40A(3) 63A(3)
IEC rated operational power
(3Phse) AC-23A/B
415V 7.5KW 9KW 11KW 15KW 18.5KW 30KW 37KW 45KW 55KW
500V
690V 11KW 15KW
Short circuit withstand current of fuse protection (kA rms expected value)
Fuse class 16A 20A 25A 32A 40A 63A 80A 100A 125A
Rated conditional
short-circuit current
50kA 25kA
Short circuit withstand current of circuit breaker for protection, any circuit breaker that can trip within 0.3s
Rated short-time
withstand current
2.5kA 3kA 5kA
Short circuit performance (unprotected)
Rated short-time withstand current 1.26kA 1.5kA 2.75kA
Rated short circuit making capacity 1.8kA 2.1kA 3.9kA
Cross area of terminals 1.5~16mm² 2.5-35mm² 10~70mm²
Rated insulation voltage Ui 800V
Rated impulse withstand voltage Uimp 8kV
Mechanical Endurance 100000
Ambient Temperature Operating -25°C…+55°C / Storage -40°C…+70°C
(1)Each pole is used as positive and negative
(2)Three poles are used in series with positive and negative poles, of which two poles are in series, and the other is negative
(3)Four poles are used in series with positive and negative poles

  • Previous:
  • Next:

  • Write your message here and send it to us