Product Detail
Product Tags
Technical Data
Temperature Range |
-40 ℉ to 150 ℉ |
Mechanical Life (no load) |
Conforms to UL and ARI specifications |
Electrical Life |
Conforms to UL and ARI specifications 94-388 thru 94-390 achieve 200,000 cycles, |
make LRA at. 5 pf, break 125% of FLA at. 75 pf at rated voltage, 10,000 cycles make |
and break LRA at.5 pf rated voltage 94-394 thru 94-369 achieve 100,000 cycles, make |
LAR at.5 pf at rated voltage 6,000 cycles make and break LEA at .5 pf rated voltage |
Weight (approximate) |
9.25 oz |
Coils Frequency |
50/60 Hz |
Coil Insulation |
Class B (130) |
Termination |
Screw and Double Q.C. |
Operate |
85% of nominal coil coltage;110% maximum safe operate |
Duty Cycle |
Continuous |
COIL DATA
Steveco Number |
Voltage |
Ress DC |
Current |
Nominal |
Max. Inrush |
30 Amp 40 Amp |
AC |
OHMS |
MA |
VA |
VA |
CJC2-388 CJC2-394 |
24 |
16.5 |
208 |
5 |
20 |
CJC2-389 CJC2-395 |
120 |
420 |
42 |
5 |
20 |
CJC2-390 CJC2-396 |
208/240 |
1825 |
21 |
5 |
20 |
Contact Ratings
Type |
Voltage |
FLA |
LRA |
RES |
CJC2-388 |
277 |
30 |
150 |
40 |
thru |
480 |
30 |
75 |
40 |
CJC2-390 |
600 |
30 |
50 |
40 |
CJC2-394 |
277 |
40 |
200 |
50 |
thru |
480 |
40 |
100 |
50 |
CJC2-396 |
600 |
40 |
80 |
50 |
Previous:
86x145mm 13A 2 Gang Switch Wall Switch with Indicator Socket Outlet
Next:
CJC2-2p 25V 30A 40V Universal Refrigeration Metal Pole Spare Parts Motor Air Conditioning Contactor