Product Detail
Product Tags
Technical Data
Standard |
IEC61008 |
Mode |
Electro-magnetic type, electronic type |
Residual current characteristics |
A, AC |
Pole No |
2P, 4P |
Rated making and breaking capacity |
500A(In=25A,40A) or 10InA(In=63A,80A,100A,125A) |
Rated current(A) |
25, 40, 63 |
Rated voltage |
AC 230(240)/400(415) |
Rated frequency |
50/60Hz |
Rated residual operating current I△n(A) |
0.03, 0.1, 0.3, 0.5 |
Rated residual non operating current I△no |
0.5I△n |
Rated conditional short-circuit current Inc |
10kA |
Rated conditional residual short-circuit Current I△c |
10kA |
Tripping duration |
instantaneous tripping ≤0.3s(0.1) |
Residual tripping current range |
0.5I△n~I△n |
Electro-mechanical endurance |
4000 cycles |
Connection capacity |
Rigid conductor 25mm² |
Terminal Connection Height |
21mm |
Connection terminal |
Pillar terminal with clamp |
Fastening torque |
2.0Nm |
Installation |
On symmetrical DIN rail 35.5mm |
Panel mounting |
Protection class |
IP20 |
Residual Current Action Breaking Time
Type |
In/A |
I△n/A |
Residual Current (I△) Is Corresponding To The Following Breaking Time (S) |
I△n |
2 I△n |
5 I△n |
5A,10A,20A,50A,100A,200A,500A |
|
general type |
any value |
any value |
0.3 |
0.15 |
0.04 |
0.04 |
Max Break-time |
S Type |
≥25 |
>0.03 |
0.5 |
0.2 |
0.15 |
0.15 |
Max Break-time |
0.13 |
0.06 |
0.05 |
0.04 |
Min non-driving time |
The general type RCBO whose current IΔn is 0.03mA or less can use 0.25A instead of 5IΔn. |