Technical Data
- Pole No.: 1, 1P+N, 2, 3, 3P+N, 4
- Rated voltage: AC 230/400V
- Rated current (A):1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63A
- Tripping curve: B, C, D
- High short-circuit breaking capacity (Icn): 10kA
- Rated service short-circuit breaking capacity(Ics): 7.5kA
- Rated frequency: 50/60Hz
- Energy limiting class: 3
- Rated impulse withstand voltage: 6.2kV
- Electro-mechanical endurance: 20000
- Contact position indication
- Connection terminal:Screw terminal/Pillar terminal with clamp
- Connection capacity: Rigid conductor up to 25mm²
- Terminal Connection Height: 19mm
- Fastening torque: 2.0Nm
- Installation:On symmetrical DIN rail 35mm/Panel mounting
Power Conumption
Rated Current Range (InA) |
Max consumption/pole (W) |
In≤10 |
3 |
10<In≤16 |
3.5 |
16<In≤25 |
4.5 |
25<In≤32 |
6 |
32<In≤40 |
7.5 |
40<In≤50 |
9 |
50<In≤63 |
13 |
Overload Current Protection Characteristics
Test Current |
Type |
Test procedure |
Initial State |
Tripping or Non-tripping Time Limit |
Expected Result |
Remark |
A |
B,C,D |
1.13In |
cold |
t≤1h |
no tripping |
|
B |
B,C,D |
1.45In |
after test a |
t<1h |
tripping |
Current in the 5s in th increase of stability |
C |
B,C,D |
2.55In |
cold |
1s<t<60s(In≤32A)/1s<t<120s(n>32A) |
tripping |
|
D |
B |
3In |
cold |
t≥0.1s |
no tripping |
Turn on the auxiliary switch to |
C |
5In |
|
D |
10In |
|
E |
B |
5In |
|
t<0.1s |
tripping |
Turn on the auxiliary switch to |
C |
10In |
cold |
D |
20In |
|