Standard | IEC60898 |
Pole NO. | 1/2/3/4 Poles |
Rated voltage | 240/415VAC |
Frequency | 50/60Hz |
Rated current | 6,10,16,20,25,32,40,50,63A |
Mechniacal life | 10,000times |
Protection degree | IP20 |
Function Feature | With over load/short circuit protection |
Enduring temperature | 55℃ |
Breaking Capacity | 4/6KA |
Rated voltage(V) | Poles | Rated current(A) | Rated short circuit breaking capacity | |
Test breaking capacity(KA) | Power factor | |||
240 | 1 | 6,10,16,20, | 6 | 0.65~0.70 |
415 | 2,3,4 | 25,32,40 | 6 | |
240 | 1,2 | 50,63 | 4 | 0.75~0.80 |
415 | 2,3,4 | 4 |
Test current | Rated current | Requested time | Result | Start station | Remark |
(A) | (A) | ||||
1.13In | All | t>=1h | Don’t trip | Cool | |
1.45In | All | T<1h | trip | heat | Current ascends the requested value stably in 5s |
2.55In | In<=32A | 1s<t<60s | trip | Cool | Auxiliary switch closed, power is on |
2.55In | In>32A | 1s<t<120s | trip | Cool | Auxiliary switch closed, power is on |
5In(Cmode) | All | t>=0.1s | Don’t trip | Cool | Auxiliary switch closed, power is on |
10In(Cmode) | All | T<0.1s | trip | Cool | Auxiliary switch closed, power is on |
10(Dmode) | All | t>=0.1s | Don’t trip | Cool | Auxiliary switch closed, power is on |
14In(Dmode) | All | T<0.1s | trip | Cool | Auxiliary switch closed, power is on |