This kind of contactor belongs to the terminal product which holding the following characteristics:normalization of installation,modularization of dimension,artistic appearance and safe for use, In addition, it adopts the equipment of direct-acting configuration.
Application instruction
Normal working and installation conditions
Type | Rated insulation voltage(V) |
Rated operating voltage(V) |
Rated heating current(A) |
Rated operating current(A) |
Control power (kW) |
AC1.AC7a Ac7b | 500 | 230 | 100 | 100/40 | 22/6 |
AC1.AC7a Ac7b | 500 | 230 | 80 | 80/30 | 16.5/4.8 |
AC1.AC7a Ac7b | 500 | 230 | 63 | 63/25 | 13/3.8 |
AC1.AC7a Ac7b | 500 | 230 | 40 | 40/15 | 8.4/2.4 |
AC1.AC7a Ac7b | 500 | 230 | 32 | 32/12 | 6.5/1.9 |
AC1.AC7a Ac7b | 500 | 230 | 25 | 25/8.5 | 5.4/1.5 |
AC1.AC7a Ac7b | 500 | 230 | 20 | 20/7 | 4/1.2 |
Operating Condition
Under the environmental temperature of -5°C~+40°C,puts rated controlling power voltage(Us) on the coil of contactor so as to make it heat to ready state,and the contactor wil close under any voltage in the range of 85%~110%.The voltage it releasing wil neither higher than 75% Us nor lowe than 20%(Us).
Type | Switching on and segmenting condition | Pick-up time (s) |
Interval (s) |
Operation frequency |
||
Ic/le | Ur/Ue | CosΦ | ||||
AC-1,AC-7a | 1.5 | 1.05 | 0.8 | 0.05 | 10 | 50 |
AC-7b | 8 | 1.05 | 0.45 | 0.05 | 10 | 50 |
Type | On condition | Segment condition | Pick-up time(s) |
Interval (s) |
Operation frequency |
||||
Ic/le | Ur/Ue | CosΦ | Ic/le | Ur/Ue | CosΦ | ||||
AC-1 | 1 | 1.05 | 0.8 | 1 | 1.05 | 0.8 | 0.05 | 10 | 6000 |
AC-7a | 1 | 1.05 | 0.8 | 1 | 1.05 | 0.8 | 0.05 | 10 | 30000 |
AC-7b | 6 | 1 | 0.45 | 1 | 0.17 | 0.45 | 0.05 | 10 | 30000 |
Mechanical Life:≥1×105 Times Electrical Life:≥3×104 Times