Standard | IEC/EN 60898-1 | ||||
Rated Current | 6A,10A,16A,20A,25A,32A,40A,50A,63A | ||||
Rated Voltage | 230/400VAC(240/415) | ||||
Rated Frequency | 50/60Hz | ||||
Number of Pole | 1P,2P,3P,4P(1P+N,3P+N) | ||||
Module size | 18mm | ||||
Curve type | B,C,D Type | ||||
Breakering capacity | 6000A | ||||
Optimumoperating temperature | -5ºC to 40ºC | ||||
Terminal Tightening torque | 5N-m | ||||
Terminal Capacity(top) | 25mm² | ||||
Terminal Capacity(bottom) | 25mm² | ||||
Electro-mechanical endurance | 4000cycles | ||||
Mounting | 35mm DinRail | ||||
Suitable Busbar | PIN Busbar |
Test | Tripping Type | Test Current | Initial State | Tripping timeor Non-tripping Time Provisior | |
a | Time-delay | 1.13In | Cold | t≤1h(In≤63A) | No Tripping |
t≤2h(ln>63A) | |||||
b | Time-delay | 1.45In | After test a | t<1h(In≤63A) | Tripping |
t<2h(In>63A) | |||||
c | Time-delay | 2.55In | Cold | 1s<t<60s(In≤63A) | Tripping |
1s<t<120s(In>63A) | |||||
d | B curve | 3In | Cold | t≤0.1s | No Tripping |
C curve | 5In | Cold | t≤0.1s | No Tripping | |
D curve | 10In | Cold | t≤0.1s | No Tripping | |
e | B curve | 5In | Cold | t≤0.1s | Tripping |
C curve | 10In | Cold | t≤0.1s | Tripping | |
D curve | 20In | Cold | t≤0.1s | Tripping |