Factory Price GV2-ME32P 24-32A 690V 3pole MPCB Motor Starter Motor Protection Circuit Breaker

Short Description:

  • GV2 Series Motor protection circuit breaker (also known as: Motor Protector or Motor starter, hereinafter referred to as “circuit breaker”) is suitable for AC voltage to 690V,the highest current to 80A circuit, is the isolation switch,circuit breaker,thermal relay function set one circuit breaker.It has isolation protection, overload protection,temperature compensation,phase break protection,short circuit protection application range: three-phase mouse cage asynchronous motor direct start and control,distribution line protection and infrequent load conversion.
  • GV2 circuit breaker complies to GB/T14048.2,GB/T14048.4, IEC60947-2, 60947-4-1 standards.

Product Detail

Product Tags

Normal work and installation conditions

  • The altitude of the installation site is generally not more than 2000m.
  • The lower limit of ambient air temperature is generally not lower than -5°C, and the upper limit is generally not higher than +40°C.
  • The relative humidity of the air is not more than 50% when the temperature is +40°C, and the minimum monthly temperature of the wettest month is 25°C, and the monthly average maximum relative humidity is not more than 90%.
  • The surrounding environment pollution level is 3.
  • Starter installation categories are lIl.
  • The inclination of the mounting surface and the vertical plane is not more than ±5°.
  • Rated work system: uninterrupted work system , Intermittent working system.

The main technical parameters

  • Rated insulation voltage Ui(V): 690.
  • Rated impulse withstand voltage Uimp(kV): 8.
  • Rated operating voltage Ue(V):230/240,400/415,440,500,690.
  • Rated frequency (Hz): 50,60.
  • Frame rated current Inm(A): 32A,80A.
  • Rated current In(A): see Table 1.
  • Hot component setting current adjustm·ent range: rated limit and rated operating short-circuit breaking capacity see Table 1.
  • The standard rated power of the three-phase motor controlled by the circuit breaker is shown in table 2.

 

Table 1

Model Fastener rated
current In (A)
Tuning current
adjustment range
(A)
Rated limit short-circuit breaking capability Icu
rated operation short-circuit breaking capability Ics kA
Arcing
distance
(mm)
400/415V 690V
Icu Ics Icu Ics
GV2-ME32(X/P) 0.16 0.1~0.16 100 100 100 100 40
GV2-ME32(X/P) 0.25 0.16~0.25 100 100 100 100 40
GV2-ME32(X/P) 0.4 0.25~0.4 100 100 100 100 40
GV2-ME32(X/P) 0.63 0.4~0.63 100 100 100 100 40
GV2-ME32(X/P) 1 0.63~1 100 100 100 100 40
GV2-ME32(X/P) 1.6 1~1.6 100 100 100 100 40
GV2-ME32(X/P) 2.5 1.6~2.5 100 100 3 2.25 40
GV2-ME32(X/P) 4 2.5~4 100 100 3 2.25 40
GV2-ME32(X/P) 6.3 4~6.3 100 100 3 2.25 40
GV2-ME32(X/P) 10 6~10 100 100 3 2.25 40
GV2-ME32(X/P) 14 9~14 15 7.5 3 2.25 40
GV2-ME32(X/P) 18 13~18 15 7.5 3 2.25 40
GV2-ME32(X/P) 23 17~23 15 6 3 2.25 40
GV2-ME32(X/P) 25 20~25 15 6 3 2.25 40
GV2-ME32(X/P) 32 24~32 10 6 3 2.25 40
GV3-ME80 25 16~25 15 7.5 4 2 50
GV3-ME80 40 25~40 15 7.5 4 2 50
GV3-ME80 63 40~63 15 7.5 4 2 50
GV3-ME80 80 56~80 15 7.5 4 2 50

 

Table 2

Model Fastener rated current In (A) Tuning current
adjustment range
(A)
Standard rated power of three-phase motor (kw)
AC-3,50Hz/60Hz
230/240V 400V 415V 440V 500V 690V
GV2-ME32(X/P) 0.16 0.1~0.16 - - - - - -
GV2-ME32(X/P) 0.25 0.16~0.25 - - - - - -
GV2-ME32(X/P) 0.4 0.25~0.4 - - - - - -
GV2-ME32(X/P) 0.63 0.4~0.63 - - - - - 0.37
GV2-ME32(X/P) 1 0.63~1 - - - 0.37 0.37 0.55
GV2-ME32(X/P) 1.6 1~1.6 - 0.37 - 0.55 0.75 1.1
GV2-ME32(X/P) 2.5 1.6~2.5 0.37 0.75 0.75 1.1 1.1 1.5
GV2-ME32(X/P) 4 2.5~4 0.75 1.5 1.5 1.5 2.2 3
GV2-ME32(X/P) 6.3 4~6.3 1.1 2.2 2.2 3 3.7 4
GV2-ME32(X/P) 10 6~10 2.2 4 4 4 5.5 7.5
GV2-ME32(X/P) 14 9~14 3 5.5 5.5 7.5 7.5 9
GV2-ME32(X/P) 18 13~18 4 7.5 9 9 9 11
GV2-ME32(X/P) 23 17~23 5.5 11 11 11 11 15
GV2-ME32(X/P) 25 20~25 5.5 11 11 11 15 18.5
GV2-ME32(X/P) 32 24~32 7.5 15 15 15 18.5 25
GV3-ME80 25 16~25 - 11 11 - - 18.5
GV3-ME80 40 25~40 - 18.5 18.5 - - 37
GV3-ME80 63 40~63 - 30 30 - - 55
GV3-ME80 80 56~80 - 37 37 - - 63

  • The enclosure protection class is lP20.
  • The operating performance of the circuit breaker is shown in Table 3.

 

Table 3

Model Rack rated
current Inm A
Hourly operation
cycles
Operation cycle number
Electrical life Mechanical Life
GV2-ME32(X/P) 32 120 10000 100000
GV3-ME80 80 120 1500 8500

GV2 GV3 Motor protection circuit breaker