·Easy to install
In addition to the same easy installation features as the smaller switch-disconnectors, these devices are extremely flexible regarding installation orientation. They work just as well in-stalled horizontally or vertically, or even on the ceiling. Smart design eliminates the need for major customization such as when using devices optimized for e.g.the 140mm switchgear busbar standard or 600mm cubicle solution.
·Space saving
All our switches have been designed for easy and cost efficient installation,maintenance and use. The modular design enables 2-pole, 3-pole and 4-pole installation with different position of the switching mechanism to suit your needs and spacial requirements. The devices can be optimized in relation to busbar and cable connections as well as handles and other accessories.
·Reliable in extreme conditions
These switch-disconnectors are extremely well suited for heavy duty applications in e.g.distribution centers with full rated current. Relevant short circuit ratings are available for lEC and UL versions alike. These devices are also equipped with extremely resistant insulation materials, which help reduce the risk of flash over between phases in even the most severe circumstances and environments.
Manual operation | |||
IEC | 160 | 315 | 630 |
200 | 400 | 800 | |
250 | |||
UL 98 file # E101914, CSA C2.22 No.4 |
200 | 400 | 600 |
Switch size | 160A | 200A | 2500A | 200A | 315A | 400A | 400A | 600A | 630A | 800A | |
IEC | Ith | 160A | 200A | 250A | 315A | 400A | 630A | 800A | |||
Ie/AC22A,415V | 160A | 200A | 250A | 315A | 400A | 630A | 800A | ||||
Ie/AC23A,415V | 160A | 200A | 250A | 315A | 400A | 630A | 800A | ||||
UL/CSA | Ampere rating | 20A | 30A | 40A | 200A | 400A | 600A |
Including protected terminal clamps lP20,except CJS-DB125FL_types.Handle and shaft are not included.
Number of poles |
Open air thermal current Ith |
Copper cable Cross section |
Rated operat currents AC22A/AC23A 400-415 V |
Type | Weight/unit |
A | mm² | A/A | kg | ||
3 | 25 | 0.75-10 | 16/16 | CJS-DB63 | 0.11 |
4 | 25 | 0.75-10 | 16/16 | CJS-DB63 | 0.14 |
3 | 32 | 0.75-10 | 25/20 | CJS-DB63 | 0.11 |
4 | 32 | 0.75-10 | 25/20 | CJS-DB63 | 0.14 |
3 | 40 | 0.75-10 | 40/23 | CJS-DB63 | 0.11 |
4 | 40 | 0.75-10 | 40/23 | CJS-DB63 | 0.14 |
3 | 63 | 1.5-35 | 63/63 | CJS-DB63 | 0.27 |
4 | 63 | 1.5-35 | 63/63 | CJS-DB63 | 0.3 |
3 | 80 | 1.5-35 | 80/75 | CJS-DB100 | 0.27 |
4 | 80 | 1.5-35 | 80/75 | CJS-DB100 | 0.3 |
3 | 115 | 10-70 | 100/80 | CJS-DB100 | 0.36 |
4 | 115 | 10-70 | 100/80 | CJS-DB100 | 0.5 |
3 | 125 | 10-70 | 125/90 | CJS-DB125 | 0.36 |
4 | 125 | 10-70 | 125/90 | CJS-DB125 | 0.5 |
3 | 125 | 125/90 | CJS-DB125 | 0.43 | |
3 | 125 | 125/90 | CJS-DB125 | 0.43 | |
3 | 125 | 125/90 | CJS-DB125 | 0.43 |
Number of poles |
Open air thermal current Ith |
Rated operat currents AC22A/AC23A 400-415 V |
Type | Weight/unit |
A | A/A | |||
3 | 200 | 200/160 | CJS-DB160 | 1.6 |
4 | 200 | 200/160 | CJS-DB160 | 2 |
3 | 200 | 200/160 | CJS-DB160 | 1.6 |
4 | 200 | 200/160 | CJS-DB160 | 2 |
3 | 200 | 200/200 | CJS-DB160 | 1.6 |
4 | 200 | 200/200 | CJS-DB200 | 2 |
3 | 200 | 200/200 | CJS-DB200 | 1.6 |
4 | 200 | 200/200 | CJS-DB200 | 2 |
3 | 250 | 250/250 | CJS-DB250 | 1.6 |
4 | 250 | 250/250 | CJS-DB250 | 2 |
3 | 250 | 250/250 | CJS-DB250 | 1.6 |
4 | 250 | 250/250 | CJS-DB250 | 2 |
3 | 315 | 315/315 | CJS-DB315 | 3.1 |
4 | 315 | 315/315 | CJS-DB315 | 3.7 |
3 | 315 | 315/315 | CJS-DB315 | 3.1 |
4 | 315 | 315/315 | CJS-DB315 | 3.7 |
3 | 400 | 400/400 | CJS-DB400 | 3.1 |
4 | 400 | 400/400 | CJS-DB400 | 3.7 |
3 | 400 | 400/400 | CJS-DB400 | 3.1 |
4 | 400 | 400/400 | CJS-DB400 | 3.7 |
3 | 630 | 630/630 | CJS-DB630 | 6.3 |
3+N 1) | 630 | 630/630 | CJS-DB630 | 6.7 |
4 | 630 | 630/630 | CJS-DB630 | 7.5 |
3 | 630 | 630/630 | CJS-DB630 | 6.3 |
4 | 630 | 630/630 | CJS-DB630 | 7.5 |
3 | 800 | 800/800 | CJS-DB800 | 6.3 |
3+N 1) | 800 | 800/800 | CJS-DB800 | 6.7 |
4 | 800 | 800/800 | CJS-DB800 | 7.5 |
3 | 800 | 800/800 | CJS-DB800 | 6.3 |
4 | 800 | 800/800 | CJS-DB800 | 7.5 |