·Altitude: ≤2000m;
·Ambient temperature: -5°C~+40°C;
·Can withstand the influence of humid air;
·Can withstand the influence of salt spray and oil mist;
·The installation category of the main circuit of the circuit breaker is III, and the installation category of the other auxiliary circuits and control circuits is ll;
·When the maximum temperature is +40°C, the relative humidity of the air does not exceed 50%. Higher relative humidity is allowed at lower humidity. Special measures should be taken to deal with occasional condensation due to temperature changes;
·The maximum inclination is 22.5°;
·In a medium with no explosion hazard, and where the medium is free of gases and conductive dust that can corrode metal and destroy insulation;
·In a place where there is no rain or snow.
·Overload long-delay action current Ir1 adjustment can be adjusted from 4 to 10 points according to different rated currents of the circuit breaker;
·The long delay action time t1 can be adjusted at 4 points;
·The short-circuit short-delay action current Ir2 can be adjusted at 10 points;
Short delay action time t2 adjustment, 4-point adjustment is available;
The short-circuit instantaneous operating current Ir3 can be adjusted at 9 or 10 points;
The pre-alarm action current Ir0 can be adjusted at 7 points;
Test terminal, used to detect the current setting value of the electronic tripper;
Electronic release working instructions;
Pre-alarm instructions;
Overload indication;
Trip button.
Model | CJM1E-125 | CJM1E-250 | CJM1E-400 | CJM1E-630 | CJM1E-800 | |||||||||||
Frame grade current Inm(A) | 125 | 250 | 400 | 630 | 800 | |||||||||||
Rated current (adjustable)In(A) | 16,20,25,32 | 32,36,40,45 50,55,60,63 |
63,65,70,75 80,85,90,95 100,125 |
100,125,140,160 180,200,225,250 |
200,225,250,280 315,350,400 |
630,640,660,680,700 720,740,760,780,800 |
630,640,660,680,700 720,740,760,780,800 |
|||||||||
Rated operating voltage Ue(V) | AC400V | |||||||||||||||
Rated insulation voltage Ui(V) | AC1000V | |||||||||||||||
Rated impulse withstand voltage (Uimp) | AC800V | |||||||||||||||
Number of poles (P) | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | ||||||
Rated ultimate short circuit breaking capacity level | M | H | M | H | M | H | M | H | M | H | ||||||
Rated ultimate short circuit breaking capacity lcu (kA) | 50 | 85 | 50 | 50 | 85 | 50 | 65 | 100 | 65 | 65 | 100 | 65 | 65 | 100 | 65 | |
Rated operating short circuit breaking capacity lcs (kA) | 35 | 50 | 35 | 35 | 50 | 35 | 42 | 65 | 42 | 42 | 65 | 42 | 42 | 65 | 42 | |
Usage categories | A | A | B | B | B | |||||||||||
Operation performance | Power on | 3000 | 3000 | 2000 | 1500 | 1500 | ||||||||||
No power | 7000 | 7000 | 4000 | 3000 | 3000 | |||||||||||
Dimensions | L | 150 | 165 | 257 | 280 | 280 | ||||||||||
W | 92 | 122 | 107 | 142 | 150 | 198 | 210 | 280 | 210 | 280 | ||||||
H | 92 | 90 | 106.5 | 115.5 | 115.5 | |||||||||||
Arcing distance | ≤50 | ≤50 | ≤106.5 | ≤100 | ≤100 |