The product realizes automatic detection and reclosing of circuit breakers.
If there is no fault, it will automatically reclose, and if there is a special fault, it will output a signal to the console.
I/O Control
When the CJ51RAi is in Auto mode, connect the device to the power supply, and use the I/O interface to remotely control the device to switch on and off.
1.Adjustable time and frequency.
2.Excessive auto-reclosing equipment will lock the product.
3.Modular assembly, more flexible installation can be adapted to more circuit breakers.
Electrical Characteristics | |
Standard | EN 50557 |
Power Distribution System | TT – TN – S |
Rated Voltage(Ue) | 230V AC (1) |
Min Rated Voltage(Min Ue) | 85% Ue |
Max Rated Voltage(Max Ue) | 110% Ue |
Rated Insulation Voltage(Ui) | 500V |
Diaelectric Strength | 2500V AC for 1 minute |
Rated Withstand Voltage(Uimp) | 4kV |
Over-voltage Category | III |
Rated Frequency | 50 |
Static Power | 1 |
Power of remote control | 20 |
Match electrical characteristics of circuit breaker | |
MCB Type | 1P – 2P – 3P – 4P C – D |
RCCB Type | AC – A – A[S] |
RCBO Type | AC – A |
Rated Current(In) | 25A – 40A – 63A – 80A – 100A |
Rated Residual Current(I△n) | 30mA – 100mA – 300mA – 500mA |
Protection Grade | IP20 (Outside the cabinet) – IP40 (Inside the cabinet) |
Terminal Part of Breaker | Soft Cable:≤ 1x16mm² hard wire:≤ 1x25mm² |
Mechanical Characteristics | |
The Width of DIN Module | 2 |
Reclosing times | Reclosing times [N]: 0~9 correspond to “0″, “1″, “2″, “3″, “4″, “5″, “6″, |
“7″, “8″, “9″ times. | |
Reclosing Time Interval | Reclosing time [T]: 0~9 correspond to “non-reclosing”, “10″, “20″, “30″, |
“45″,”60″, “90″, “120″, “150″, “180″ seconds | |
Max Operation Frequency | 30 |
Maximum mechanical durability (total number of operations) | 10000 |
Max. Auto Reclose Cycle | Reclosing times can be set |
Enviroment Characterisics | |
Pollution Grade | 2 |
Work Temperatur | -25°C +60°C |
Storage Temperature | -40°C +70°C |
Relative Humidity | 55°C – RH 95% |
Characteristics of auxiliary contacts in opening and closing state | |
Opening and closing status | yes |
Contact Type | Electronic Relay |
Rated Voltage | 5V-230V AC/DC |
Rated Current | 0.6 A(min) -3A (max) |
Frequency | 50Hz |
Use category | AC12 |
Operation mode | NO\NC\COM Signal of Handle Position |
Cable Connection | ≤ 2.5mm² |
Rated Tightening Torque | 0.4Nm |
Auto Reclose Function | |
Auto recloser | √ |
Reclose Stops when Fault | √ |
Signal of Reclosing | √ |
Fault Signal Indicator | √ |
Reclosing function on/off | √ |
Auxiliary Contact for Remote Operation | √ |
Internal Electrical Protection | √ |