Our solutions are widely recognized and trusted by consumers and will meet up with constantly developing financial and social requires for Hot Sale for CJW1 2000A Drawout Type Air Circuit Breaker 3p 4p Acb, We keep on with supplying integration alternatives for customers and hope to create long-term, steady, sincere and mutual advantageous interactions with consumers. We sincerely anticipate your check out.
Our solutions are widely recognized and trusted by consumers and will meet up with constantly developing financial and social requires for China Universal Circuit Breaker and Acb, At Existing, our products have been exported to more than sixty countries and different regions, such as Southeast Asia, America, Africa, Eastern Europe, Russia, Canada etc. We sincerely hope to establish wide contact with all potential customers both in China and the rest part of the world.
Rated current Table 1 | ||||||||
Rated frame current Inm A | Rated current ln A | |||||||
2000 | (400)630,800,1000,1250,1600,2000 | |||||||
3200 | 2000,2500,2900,3200 | |||||||
4000 | 3200,3600,4000 | |||||||
6300 | 4000,5000,6300 |
The rated short circuit breaking capability and short time withstand of the breakers, the arcing distance is “zero” (as the outside of the breaker is no arcing.)Table 2
Rated frame current Inm A | 2000 | 3200 | 4000 | 6300 | ||||
Rated limit short circuit breaking capability lcu(kA)O-CO |
400V | 80 | 80 | 100 | 120 | |||
690V | 50 | 50 | 75 | 85 | ||||
Rated working short circuit breaking capability n x lcu(KA)/COS∅ |
400V | 176/0.2 | 176/0.2 | 220/0.2 | 264/0.2 | |||
690V | 105/0.25 | 105/0.25 | 165/0.2 | 187/0.2 | ||||
Rated short time withstand lcw lcs(kA)O-CO-CO |
400V | 50 | 50 | 80 | 100 | |||
690V | 40 | 40 | 65 | 75 | ||||
Rated short time withstand lcw (kA)———”+0.4s,O-CO |
400V | 50 | 50 | 65/80(MCR) | 85/100(MCR) | |||
690V | 40 | 40 | 50/65(MCR) | 65/75(MCR) | ||||
Notice: The input and out put wire are the same for the breaking of the capability. |
The maximum destroy power is 360W for the breakers, and in the different temperature,and rated lasting current will change.Table 3
Ambient temperature℃ |
Rated current | |||||||
400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A | ||
40 | 400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A | |
50 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1900A | |
60 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1800A |
Intelligent over current controller protection feature and functions The setting and error.Table 4
Long delay | Short delay | Instantaneous | Earthed error | |||||
lr1 | lr2 | Error | lr3 | Error | lr4 | Error | ||
(0.4-1)In | (0.4-15)In | ±10% | ln-50kA(Inm=2000A) ln-75kA(Inm=3200A) |
±15% | lnm=2000~3200A (0.2-0.8)In (1200A,160A) |
±10% | ||
Notice:lf it has the three steps protection at the same time, the setting will not across. |
Long delay over current inverse time ooperation features I2TL, =(1.51lr1)2tL, and its action time(1.02-2.0) Ir1, has time error is ±15%. Table 5
1.05Ir1 | 1.3Ir1 | 1.5Ir1 Setting time S |
15 | 30 | 60 | 120 | 240 | 480 |
>2hno action | <1h action | 2.0Ir Setting time S | 8.4 | 16.9 | 33.7 | 67.5 | 135 | 270 |
Our solutions are widely recognized and trusted by consumers and will meet up with constantly developing financial and social requires for Hot Sale for CJW1 2000A Drawout Type Air Circuit Breaker 3p 4p Acb, We keep on with supplying integration alternatives for customers and hope to create long-term, steady, sincere and mutual advantageous interactions with consumers. We sincerely anticipate your check out.
Hot Sale for China Universal Circuit Breaker and Acb, At Existing, our products have been exported to more than sixty countries and different regions, such as Southeast Asia, America, Africa, Eastern Europe, Russia, Canada etc. We sincerely hope to establish wide contact with all potential customers both in China and the rest part of the world.