Our team through professional training. Skilled professional knowledge, strong sense of service, to meet the service needs of customers for Intelligent universal circuit breaker: escorting the circuit, Sincerely hope we are rising up along with our shoppers everywhere in the world.
Our team through professional training. Skilled professional knowledge, strong sense of service, to meet the service needs of customers for , We’re your reliable partner in international markets with the best quality goods. Our advantages are innovation, flexibility and reliability which have been built during the last twenty years. We focus on providing service for our clients as a key element in strengthening our long-term relationships. Our continual availability of high grade solutions in combination with our excellent pre-sales and after-sales service ensures strong competitiveness in an increasingly globalized market.
Rated current Table 1 | ||||||||
Rated frame current Inm A | Rated current ln A | |||||||
2000 | (400)630,800,1000,1250,1600,2000 | |||||||
3200 | 2000,2500,2900,3200 | |||||||
4000 | 3200,3600,4000 | |||||||
6300 | 4000,5000,6300 |
The rated short circuit breaking capability and short time withstand of the breakers, the arcing distance is “zero” (as the outside of the breaker is no arcing.)Table 2
Rated frame current Inm A | 2000 | 3200 | 4000 | 6300 | ||||
Rated limit short circuit breaking capability lcu(kA)O-CO |
400V | 80 | 80 | 100 | 120 | |||
690V | 50 | 50 | 75 | 85 | ||||
Rated working short circuit breaking capability n x lcu(KA)/COS∅ |
400V | 176/0.2 | 176/0.2 | 220/0.2 | 264/0.2 | |||
690V | 105/0.25 | 105/0.25 | 165/0.2 | 187/0.2 | ||||
Rated short time withstand lcw lcs(kA)O-CO-CO |
400V | 50 | 50 | 80 | 100 | |||
690V | 40 | 40 | 65 | 75 | ||||
Rated short time withstand lcw (kA)———”+0.4s,O-CO |
400V | 50 | 50 | 65/80(MCR) | 85/100(MCR) | |||
690V | 40 | 40 | 50/65(MCR) | 65/75(MCR) | ||||
Notice: The input and out put wire are the same for the breaking of the capability. |
The maximum destroy power is 360W for the breakers, and in the different temperature,and rated lasting current will change.Table 3
Ambient temperature℃ |
Rated current | |||||||
400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A | ||
40 | 400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A | |
50 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1900A | |
60 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1800A |
Intelligent over current controller protection feature and functions The setting and error.Table 4
Long delay | Short delay | Instantaneous | Earthed error | |||||
lr1 | lr2 | Error | lr3 | Error | lr4 | Error | ||
(0.4-1)In | (0.4-15)In | ±10% | ln-50kA(Inm=2000A) ln-75kA(Inm=3200A) |
±15% | lnm=2000~3200A (0.2-0.8)In (1200A,160A) |
±10% | ||
Notice:lf it has the three steps protection at the same time, the setting will not across. |
Long delay over current inverse time ooperation features I2TL, =(1.51lr1)2tL, and its action time(1.02-2.0) Ir1, has time error is ±15%. Table 5
1.05Ir1 | 1.3Ir1 | 1.5Ir1 Setting time S |
15 | 30 | 60 | 120 | 240 | 480 |
>2hno action | <1h action | 2.0Ir Setting time S | 8.4 | 16.9 | 33.7 | 67.5 | 135 | 270 |
Our team through professional training. Skilled professional knowledge, strong sense of service, to meet the service needs of customers for Manufactur standard Just a moment…, Sincerely hope we are rising up along with our shoppers everywhere in the world.
Manufactur standard , We’re your reliable partner in international markets with the best quality goods. Our advantages are innovation, flexibility and reliability which have been built during the last twenty years. We focus on providing service for our clients as a key element in strengthening our long-term relationships. Our continual availability of high grade solutions in combination with our excellent pre-sales and after-sales service ensures strong competitiveness in an increasingly globalized market.