• nybjtp

Manufacturer CDFH-1000VDC 10x38mm 30A Fuse holder for solar system

Short Description:

CDFH series fuse holder is made of refractory material, and meets the standard of IEC 60947-3. The maximum rated voltage is 1000V and the maximum current is 30A. As a short circuit and over-current protector, it is widely used in the high and low voltage distribution system, control system, and electrical equipments, like distribution box and inverter.


Product Detail

Product Tags

Product Benefits

  • DIN35 Rail Installation, Easy to Install
  • Adjustable terminal block, Wiring firm
  • Fire-retardant shell, high temperature resistance
  • Flexible installation, Easy to replace

 

Technical data

Standard IEC60947-3
PV DC CDFH Fuse Holder Pole 1P
Rated Working Voltage 1000VDC
Rated Current 30A
Breaking Capacity 20kA
Max Power Dissipation 3W
Connection and InstallationWire 2.5mm²-6.0mm²
Terminal Screws M3.5
Torque 0.8~1.2N.m
Degree of Protection IP20
Fuse Size 10x38mm
Operating Temperature Range -30°C~+70°C
Mounting DIN rail IEC/EN 60715
Pollution Degree 3
Relative Humidity +20°C ≤95%, +40°C ≤50%
Installation Class III
Weight 0.07kg Per pole

 

 

DC Fuse holder 07

 

Photovoltaic Fuses 10x38mm

 

Product Benefits

  • Amps:1~32A; Volts: 1000VDC;Breaking Capacity:30kA
  • Compact design.Low power loss.Excellent DC performance
  • Low arc voltage and low energy let-through(I2t)
  • Product storage temperature: -40°C~120°C. At 40°CC, the relative humidity is not more than 70%, below 30°C, not more than 80%, below 20°C, not more than 90%
  • Packaging and storage temperature: -40°C~80°C. The relative humidity is not more than 90%, and there is no condensation

Vibration and Shock Resistance

  • It has good resistance to vibration and impact, and can withstand more than 20g Comply with the IT application environment of rail transit and the use of general motor vehicles.
  • In the application environment with strong vibration, the corresponding test can be negotiated, which generally needs a long period.

Altitude

  • 2000 – 4500m
  • Higher altitude mainly leads to insulation deterioration, heat dissipation condition deterioration and air pressure change.

A) The temperature rise of the fuse increases by 0.1-0.5k every 100m above sea level.
B) For every 100m increase in altitude, the average ambient temperature decreases by about 0.5K.
C) In open environment, the influence of altitude on rated current can be ignored.
D) When used in a closed environment, if the air temperature or box temperature does not decrease with the increase of altitude and still reaches more than 40°C,  the rated current needs to be reduced. The rated current shall be reduced by 2%-5% for every 1000m increase in altitude.

  • Effect of altitude on air insulation strength (breakdown strength)

A) Within 2000-4500m, the insulation strength decreases by 12-15% for every 1000m increase in altitude
B) the insulation gap between the fuse and other live structures and to the ground shall be considered by the user.

 

DC Fuse holder 08