Construction and feature
- CJRX16 Auxiliary, through a combination of different component and assembly,achieved function of Shunt tripper, under-voltage tripper, auxiliary contact, Shunt tripper + auxiliary contact and Under-voltage tripper + auxiliary contact.
- The handles of these 5 products are designed with mid-position and without midposition.
- The product has a transparent clamshell to put tags in and characteristic stripes on both sides.
- It is featured with elegant appearance, complete function and small volume.
- In same housing, through a combination of different component and assembly,achieved auxiliary contact、remote shunt trip and under-voltage protect.
Shunt tripper
- Rated voltage: AC 230V
- Moving voltage: (70%~110%) x Ue
Under-voltage tripper
- Rated voltage: AC 230V
- Moving voltage: (35%~70%) x Ue
- Guaranteed closing voltage: (85%~110%) x Ue
Outline and Mounting Dimension
Auxiliary Contact
1NO+1NC (1 normal open+ 1 normal close)
Usage category |
Rated current (A) |
Rated Voltage(V) |
AC12 |
3 |
400 |
6 |
230 |
DC12 |
6 |
24 |
2 |
48 |
1 |
130 |