Our items are commonly identified and trusted by customers and may fulfill continuously switching economic and social wants of New Style Afdd RCBO Combined 4pole 6ka Breaking Capacity 32A Afdd Arc Fault Detection Devices, We promise to try our best to provide you with high quality and efficient services.
Our items are commonly identified and trusted by customers and may fulfill continuously switching economic and social wants of C&J Afdd and RCBO, Insisting over the high-quality generation line management and prospects guide provider, we’ve made our resolution to supply our shoppers using the initially stage purchasing and soon after provider working experience. Preserving the prevailing helpful relations with our prospects, we even now innovate our product lists the many time to meet up with the brand new wants and stick to the latest trend of this business in Ahmedabad. We’re ready to facial area the difficulties and make the transform to grasp many of the possibilities in international trade.
Standard | IEC/BS/EN62606,IEC/AS/NZS 61009.1 (RCBO) | ||||
Rated current | 6,10,13,16,20,25,32,40A | ||||
Rated voltage | 230/240V AC | ||||
Rated frequency | 50/60Hz | ||||
Maximum operating voltage | 1.1Un | ||||
Minimum operating voltage | 180V | ||||
Protection degree | IP20 /IP40 (Terminals/Housing) | ||||
Type & mounting arrangement | Din-Rail | ||||
Application | Consumer unit | ||||
Tripping curve | B,C | ||||
Rated residual making and breaking capacity (I△m) | 2000A | ||||
Mechanical operations | >10000 | ||||
Electrical operations | ≥1200 | ||||
Rated residual operating current (I△n) | 10,30,100,300mA | ||||
Rated short-circuit capacity (Icn) | 6kA | ||||
AFDD Test means | Automatic test function as per 8.17 IEC 62606 | ||||
Classification as per IEC 62606 | 4.1.2 – AFDD unit integrated in a protective device | ||||
Ambient operating temperature | -25°C to 40°C | ||||
AFDD ready indication | Single LED Indication | ||||
Overvoltage function | Overvoltage condition of 270Vrms to 300Vrms for 10 seconds will cause device to trip.LED indication of over-voltage trip will be provided on product re-latch. | ||||
Self test interval | 1 Hour | ||||
Earth fault current | Trip time limit (typical measured value) | ||||
0.5 x Idn | No trip | ||||
1 x Idn | <300 ms (nominally <40 ms) | ||||
5 x Idn | <40ms (nominally <40 ms)Actual Tripping Threshold |
■LED Indication:
□After tripping under a fault condition the fault status indicator will show the fault nature according to the table opposite.
□LED flashing sequence repeats every 1.5sec for next 10 sec after powering up
■Series Arc Fault:
□1 Flash – Pause – 1 Flash – Pause – 1 Flash
■Parallel Arc Fault:
□1 2 Flashes – Pause – 2 Flashes – Pause – 2 Flashes
■Over Voltage Fault:
□3 Flashes – Pause – 3 Flashes – Pause – 3 Flashes
■Self-Test Fault:
□1 Flash – Pause -1 Flash – Pause -1 Flash (At Double Rate)
Our items are commonly identified and trusted by customers and may fulfill continuously switching economic and social wants of New Style Afdd RCBO Combined 4pole 6ka Breaking Capacity 32A Afdd Arc Fault Detection Devices, We promise to try our best to provide you with high quality and efficient services.
New Style C&J Afdd and RCBO, Insisting over the high-quality generation line management and prospects guide provider, we’ve made our resolution to supply our shoppers using the initially stage purchasing and soon after provider working experience. Preserving the prevailing helpful relations with our prospects, we even now innovate our product lists the many time to meet up with the brand new wants and stick to the latest trend of this business . We’re ready to facial area the difficulties and make the transform to grasp many of the possibilities in international trade.