We emphasize development and introduce new products into the market every year for Super Lowest Price CEJIA Afdd-32 Arc Fault Circuit Breaker Afdd for Top Sales Electrical Fire Protection Circuit Breaker Afdd Manufacturer 10A 16A 20A 32A 40A 63A Europe Market 6ka, We believe that a passionate, revolutionary and well-trained team should be able to establish great and mutually beneficial business enterprise relationships with you soon. Please truly feel no cost to get hold of us for additional details.
We emphasize development and introduce new products into the market every year for China Arc Fault Circuit Interrupter and Afdd, As an experienced factory we also accept customized order and make it same as your picture or sample specifying specification and customer design packing. The main goal of the company is to live a satisfactory memory to all the customers, and establish a long term win-win business relationship. For more information, please contact us. And It is our great pleasure if you like to have a personally meeting in our office.
Standard | IEC/BS/EN62606,IEC/AS/NZS 61009.1 (RCBO) | ||||
Rated current | 6,10,13,16,20,25,32,40A | ||||
Rated voltage | 230/240V AC | ||||
Rated frequency | 50/60Hz | ||||
Maximum operating voltage | 1.1Un | ||||
Minimum operating voltage | 180V | ||||
Protection degree | IP20 /IP40 (Terminals/Housing) | ||||
Type & mounting arrangement | Din-Rail | ||||
Application | Consumer unit | ||||
Tripping curve | B,C | ||||
Rated residual making and breaking capacity (I△m) | 2000A | ||||
Mechanical operations | >10000 | ||||
Electrical operations | ≥1200 | ||||
Rated residual operating current (I△n) | 10,30,100,300mA | ||||
Rated short-circuit capacity (Icn) | 6kA | ||||
AFDD Test means | Automatic test function as per 8.17 IEC 62606 | ||||
Classification as per IEC 62606 | 4.1.2 – AFDD unit integrated in a protective device | ||||
Ambient operating temperature | -25°C to 40°C | ||||
AFDD ready indication | Single LED Indication | ||||
Overvoltage function | Overvoltage condition of 270Vrms to 300Vrms for 10 seconds will cause device to trip.LED indication of over-voltage trip will be provided on product re-latch. | ||||
Self test interval | 1 Hour | ||||
Earth fault current | Trip time limit (typical measured value) | ||||
0.5 x Idn | No trip | ||||
1 x Idn | <300 ms (nominally <40 ms) | ||||
5 x Idn | <40ms (nominally <40 ms)Actual Tripping Threshold |
■LED Indication:
□After tripping under a fault condition the fault status indicator will show the fault nature according to the table opposite.
□LED flashing sequence repeats every 1.5sec for next 10 sec after powering up
■Series Arc Fault:
□1 Flash – Pause – 1 Flash – Pause – 1 Flash
■Parallel Arc Fault:
□1 2 Flashes – Pause – 2 Flashes – Pause – 2 Flashes
■Over Voltage Fault:
□3 Flashes – Pause – 3 Flashes – Pause – 3 Flashes
■Self-Test Fault:
□1 Flash – Pause -1 Flash – Pause -1 Flash (At Double Rate)
We emphasize development and introduce new products into the market every year for Super Lowest Price CEJIA Afdd-32 Arc Fault Circuit Breaker Afdd for Top Sales Electrical Fire Protection Circuit Breaker Afdd Manufacturer 10A 16A 20A 32A 40A 63A Europe Market 6ka, We believe that a passionate, revolutionary and well-trained team should be able to establish great and mutually beneficial business enterprise relationships with you soon. Please truly feel no cost to get hold of us for additional details.
Super Lowest Price China Arc Fault Circuit Interrupter and Afdd, As an experienced factory we also accept customized order and make it same as your picture or sample specifying specification and customer design packing. The main goal of the company is to live a satisfactory memory to all the customers, and establish a long term win-win business relationship. For more information, please contact us. And It is our great pleasure if you like to have a personally meeting in our office.