The corporate upholds the philosophy of “Be No.1 in quality, be rooted on credit rating and trustworthiness for growth”, will proceed to serve aged and new buyers from home and abroad whole-heatedly for Wholesale OEM/ODM CJw1-1000 3p 800A 220V Drawer Type Acb Air Circuit Breaker, We have been in operation for more than 10 years. We are dedicated to quality products and consumer support. We invite you to visit our company for a personalized tour and advanced business guidance.
The corporate upholds the philosophy of “Be No.1 in quality, be rooted on credit rating and trustworthiness for growth”, will proceed to serve aged and new buyers from home and abroad whole-heatedly for China Air Circuit Breaker and China Local Brand Acb, With the advanced workshop, qualified design team and strict quality control system, based on mid- to high-end marked as our marketing positioning, our merchandise are fast selling onto European and American markets with our own brands such as below Deniya, Qingsiya and Yisilanya.
Rated current Table 1 | ||||||||
Rated frame current Inm A | Rated current ln A | |||||||
2000 | (400)630,800,1000,1250,1600,2000 | |||||||
3200 | 2000,2500,2900,3200 | |||||||
4000 | 3200,3600,4000 | |||||||
6300 | 4000,5000,6300 |
The rated short circuit breaking capability and short time withstand of the breakers, the arcing distance is “zero” (as the outside of the breaker is no arcing.)Table 2
Rated frame current Inm A | 2000 | 3200 | 4000 | 6300 | ||||
Rated limit short circuit breaking capability lcu(kA)O-CO |
400V | 80 | 80 | 100 | 120 | |||
690V | 50 | 50 | 75 | 85 | ||||
Rated working short circuit breaking capability n x lcu(KA)/COS∅ |
400V | 176/0.2 | 176/0.2 | 220/0.2 | 264/0.2 | |||
690V | 105/0.25 | 105/0.25 | 165/0.2 | 187/0.2 | ||||
Rated short time withstand lcw lcs(kA)O-CO-CO |
400V | 50 | 50 | 80 | 100 | |||
690V | 40 | 40 | 65 | 75 | ||||
Rated short time withstand lcw (kA)———”+0.4s,O-CO |
400V | 50 | 50 | 65/80(MCR) | 85/100(MCR) | |||
690V | 40 | 40 | 50/65(MCR) | 65/75(MCR) | ||||
Notice: The input and out put wire are the same for the breaking of the capability. |
The maximum destroy power is 360W for the breakers, and in the different temperature,and rated lasting current will change.Table 3
Ambient temperature℃ |
Rated current | |||||||
400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A | ||
40 | 400A | 630A | 800A | 1000A | 1250A | 1600A | 2000A | |
50 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1900A | |
60 | 400A | 630A | 800A | 1000A | 1250A | 1550A | 1800A |
Intelligent over current controller protection feature and functions The setting and error.Table 4
Long delay | Short delay | Instantaneous | Earthed error | |||||
lr1 | lr2 | Error | lr3 | Error | lr4 | Error | ||
(0.4-1)In | (0.4-15)In | ±10% | ln-50kA(Inm=2000A) ln-75kA(Inm=3200A) |
±15% | lnm=2000~3200A (0.2-0.8)In (1200A,160A) |
±10% | ||
Notice:lf it has the three steps protection at the same time, the setting will not across. |
Long delay over current inverse time ooperation features I2TL, =(1.51lr1)2tL, and its action time(1.02-2.0) Ir1, has time error is ±15%. Table 5
1.05Ir1 | 1.3Ir1 | 1.5Ir1 Setting time S |
15 | 30 | 60 | 120 | 240 | 480 |
>2hno action | <1h action | 2.0Ir Setting time S | 8.4 | 16.9 | 33.7 | 67.5 | 135 | 270 |
The corporate upholds the philosophy of “Be No.1 in quality, be rooted on credit rating and trustworthiness for growth”, will proceed to serve aged and new buyers from home and abroad whole-heatedly for Wholesale OEM/ODM CJW1-1000 3p 800A 220V Drawer Type Acb Air Circuit Breaker, We have been in operation for more than 10 years. We are dedicated to quality products and consumer support. We invite you to visit our company for a personalized tour and advanced business guidance.
Wholesale OEM/ODM China Air Circuit Breaker and China local Brand Acb, With the advanced workshop, qualified design team and strict quality control system, based on mid- to high-end marked as our marketing positioning.