Circuit breaker rating
Model | Frame rating rated current In(mA) |
Rated current In(A) |
Rated working voltage (V) |
Rated Insulation voltage (V) |
Rated ultimate short circuit breaking capacity Icu(kA) |
Rated operating short-circuit breaking capacity Ics(kA) |
Number of poles |
Flashover distance (mm) |
CJMM3-125S | 125 | 16,20,25,32, 40,50,60,80, 100,125 |
400/415 | 1000 | 25 | 18 | 3P | ≤50 |
CJMM3-125H | 125 | 35 | 25 | 3P | ||||
CJMM3-250S | 250 | 100,125,160, 180,200,225, 250 |
400/690 | 800 | 35/10 | 25/5 | 2P,3P,4P | ≤50 |
CJMM3-250S | 250 | 600 | 50 | 35 |
Inverse time breaking action characteristics of overcurrent release of distribution circuit breaker when all poles are energized at the same time
Test current name | I/In | Appointed time | Starting state |
Agreed no tripping current | 1.05 | 2h(In>63A),1h(In≤63A) | Cold state |
Agreed tripping current | 1.3 | 2h(In>63A),1h(In≤63A) | Immediately after the sequence 1 test, start |
Inverse time breaking action characteristics of overcurrent release of circuit breaker for motor protection when all poles are energized at the same time
Setting current | Appointed time | Starting state | Remark |
1.0In | >2h | Cold state | |
1.2In | ≤2h | Immediately after the sequence 1 test, start | |
1.5In | ≤4min | cold state | 10 ≤ In ≤ 250 |
≤8min | cold state | 250 ≤ In ≤ 630 | |
7.2In | 4s≤T≤10s | cold state | 10 ≤ In ≤ 250 |
6s≤T≤20s | cold state | 250 ≤ In ≤ 800 |
The instantaneous operating characteristics of the circuit breaker for distribution are set to 10In±20%, and the instantaneous operating characteristics of the circuit breaker for motor protection are set to 12In±20%.