Basic technical data of contactor (Table 1)
Model of contactor |
Conventional heating current(A) |
Rated working current(A) |
Max power of controlled 3-phase cage motor(KW) |
Operation cycles per hour |
Electrical lifetime (10^4 times) |
Mechanical lifetime (10^4 times) |
Matching fuse(SCPD) |
|||
AC-3 | AC-4 | AC-3 | Times/h | Model | Rated current |
|||||
380V | 690V | 380V | 690V | AC-3 | ||||||
CJX2F-115(Z) | 200 | 115 | 86 | 55 | 80 | 1200 | 120 | 1000 | RT16-1 | 200 |
CJX2F-150(Z) | 200 | 150 | 108 | 75 | 100 | 1200 | 120 | 1000 | RT16-1 | 225 |
CJX2F-185(Z) | 275 | 185 | 118 | 90 | 110 | 600 | 100 | 600 | RT16-2 | 315 |
CJX2F-225(Z) | 275 | 225 | 137 | 110 | 129 | 600 | 100 | 600 | RT16-2 | 315 |
CJX2F-265(Z) | 315 | 265 | 170 | 132 | 160 | 600 | 80 | 600 | RT16-2 | 355 |
CJX2F-330(z) | 380 | 330 | 235 | 160 | 220 | 600 | 80 | 600 | RT16-3 | 450 |
CJX2F-400(Z) | 450 | 400 | 303 | 200 | 280 | 600 | 80 | 600 | RT16-3 | 460 |
CJX2F-500 | 630 | 500 | 353 | 250 | 335 | 600 | 80 | 600 | RT16-4 | 750 |
CJX2F-630 | 800 | 630 | 462 | 335 | 450 | 600 | 80 | 600 | RT16-4 | 950 customize |
CJX2F-800 | 800 | 800 (AC-3) |
486 (AC-3) |
450 | 475 | 600 | 60 | 300 | N4 | 1000 |
CJX2F-800 | 800 | 630 (AC-4) |
462 (AC-4) |
335 | 450 | 600 | 60 | 300 | N4 | 1000 |
Model of auxiliary contact |
Number of contact | Rated insulation Voltage (V) |
Controlled capacity | |
Number of NO | Number of NC | |||
F4-02 | 0 | 2 | 660 | AC-15 360VA DC-13 33W |
F4-11 | 1 | 1 | ||
F4-20 | 2 | 0 | ||
F4-40 | 4 | 0 | ||
F4-31 | 3 | 1 | ||
F4-22 | 2 | 2 | ||
F4-13 | 1 | 3 | ||
F4-04 | 0 | 4 |
Performance characteristic
·Pull-in voltage is 85%~110%,US
·The common contactor’s release voltage is 20%~75%Us,the energy-saving product’s release voltage is 10%~75%Us
·CJX2F contactor’s rated impulse withstand voltage is 8KV; Rated limit short circuit current is 50KA and the compatible type with SCPD is type-l.
Model | CIX2F-115~265: 50Hz; CJX2F-330~800: 40~400Hz | |||||
110(AC) | 127(AC) | 220(AC) | 380(AC) | Power(VA) | ||
Pick-up | Holding | |||||
CJX2F-115,150 | FF110 | FF127 | FF220 | FF380 | 660 | 85.5 |
CJX2F-185,225 | FG110 | FG127 | FG220 | FG380 | 966 | 91.2 |
CJX2F-265 | FH110 | FH127 | FH220 | FH380 | 840 | 150 |
CJX2F-330 | FL110 | FL127 | FL220 | FL380 | 1500 | 34.2 |
CJX2F-400 | FJ110 | FJ127 | FJ220 | FJ380 | 1500 | 34.2 |
CJX2F-500 | FK110 | FK127 | FK220 | FK380 | 1500 | 34.2 |
CJX2F-630 | FL110 | FL127 | FL220 | FL380 | 1700 | 34.2 |
CJX2F-800 | FM110 | FM127 | FM220 | FM380 | 1700 | 34.2 |
Annotation: only coils of 3 poles and 4 poles products of CJX2F-330 and CJX2F-400 are compatible.
Model | 48(DC) | 110(DC) | 220(DC) | Power(VA) | |
Pick-up | Holding | ||||
CJX2F-115Z,150Z | FF 48 DC | FF 110 DC | FF 220 DC | 1500 | 15 |
CJX2F-185Z,225Z | FG 48 DC | FG 110 DC | FG 220 DC | 1800 | 15 |
CJX2F-265Z | FH 110 DC | FH 220 DC | 1500 | 15 | |
CJX2F-330Z | FI 110 DC | FI 220 DC | 1500 | 15 | |
CJX2F-400Z | FJ 110 DC | FJ 220 DC | 1800 | 15 |
AC contactors are important components in electrical systems and are used to control the flow of current to various devices. As far as AC contactors go, the CJX2 series and CJX2F series are two popular choices, but they differ greatly.
CJX2 series AC contactors are a widely used type known for their reliable performance and durability. It is designed for general purpose applications and is suitable for controlling circuits up to 660V AC. The CJX2 Series is popular in a wide range of industrial and commercial environments due to its compact size and ease of installation.
On the other hand, CJX2F series AC contactors are designed for frequent operation and are equipped with auxiliary contacts for signaling purposes. This series is ideally suited for applications requiring high frequency switching, such as conveyor systems, elevators and cranes. The CJX2F Series is designed to withstand the wear and tear of frequent use, making it the first choice for demanding environments.
One of the main differences between the two series is their structure. The CJX2F Series features a reinforced frame and enhanced contact materials, allowing it to handle the repetitive stress of frequent switching without compromising performance. In addition, the CJX2F series is equipped with a wider coil voltage range, providing greater flexibility for various electrical systems.
In terms of compatibility, the CJX2 series and CJX2F series are not interchangeable due to different designs and functions. It is important to select the correct series based on the specific requirements of the application to ensure optimal performance and longevity.
In summary, although both CJX2 series and CJX2F series AC contactors have the same basic purpose of controlling circuits, their unique features make them suitable for different applications. Understanding the differences between these series is critical to selecting the appropriate AC contactor for a specific electrical system, ultimately ensuring efficient and reliable operation.